The Siemens 3VA2010-5HN46-0AA0 is a SENTRON molded case circuit breaker for line protection, rated 100 A continuous across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Four poles, ETU350 electronic trip unit, and interrupting ratings from 187 kA at 240 V down to 3 kA at 690 V. The 187 kA at 240 V figure means this breaker handles very high available fault current on low-voltage transformer secondaries without cascading upstream.
Panel footprint: 140 mm wide, 181 mm tall, 86 mm deep — four-pole MCCB. IP40 on the front face. The ETU350 is powered from the breaker's own current sensors — no auxiliary control power required for trip functionality.