Skip to main content
Siemens 3VA2010-5HN46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-5HN46-0AA0 SENTRON MCCB, 100 A, 4-Pole, ETU3

MPN3VA2010-5HN46-0AA0
Active

Siemens SENTRON 3VA2 molded case circuit breaker, 100 A, 4-pole, ETU350 electronic trip unit, line protection design, 187 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2010-5HN46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2010-5HN46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.13.5 W

Protection & Trip Unit

3VA2010-5HN46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2010-5HN46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2010-5HN46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2010-5HN46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2010-5HN46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

The Siemens 3VA2010-5HN46-0AA0 is a SENTRON molded case circuit breaker for line protection, rated 100 A continuous across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Four poles, ETU350 electronic trip unit, and interrupting ratings from 187 kA at 240 V down to 3 kA at 690 V. The 187 kA at 240 V figure means this breaker handles very high available fault current on low-voltage transformer secondaries without cascading upstream.

Panel footprint: 140 mm wide, 181 mm tall, 86 mm deep — four-pole MCCB. IP40 on the front face. The ETU350 is powered from the breaker's own current sensors — no auxiliary control power required for trip functionality.

Frequently asked questions

What is the difference between 3VA2010-5HN46-0AA0 and the 3VA1110-5ED36-0AA0?

The 3VA2010-5HN46-0AA0 uses an ETU350 electronic trip unit with adjustable curves and ground-fault protection, while the 3VA1110-5ED36-0AA0 uses a fixed thermal-magnetic trip. The 3VA2 is the right choice when you need selective coordination and adjustable time delays; the 3VA1 is a simpler, lower-cost option for basic overload and short-circuit protection.

MPN
3VA2010-5HN46-0AA0