Siemens 3VA2010-5JQ36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-5JQ36-0AA0 SENTRON MCCB, 100 A, 3-Pole, 187

MPN3VA2010-5JQ36-0AA0
Active

Siemens SENTRON 3VA2010-5JQ36-0AA0, molded case circuit breaker (MCCB), 3-pole, 100 A continuous rated current, line protection design, breaking capacity 187 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2010-5JQ36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2010-5JQ36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.13.5 W
3VA2010-5JQ36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes
3VA2010-5JQ36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2010-5JQ36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2010-5JQ36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2010-5JQ36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

At 415 V and 440 V it still holds 121 kA, dropping to 75.6 kA at 500 V and 3 kA at 690 V, so the voltage class of your distribution panel directly governs which breaking capacity applies.

That 105 mm width on a 3-pole 100 A frame means it occupies roughly four 27 mm DIN positions — useful when laying out a multi-breaker sub-feed panel or retrofitting into an existing SENTRON switchboard. Maximum power loss is 13.5 W, so ventilation in a sealed enclosure should account for that thermal load at rated current.

Ground-fault and communication capability

Communication function is present, supporting integration into a higher-level monitoring or energy management system. Designed for line protection duty, not motor or feeder protection.

Frequently asked questions

Where can I buy 3VA2010-5JQ36-0AA0 and how is it quoted?

This MCCB is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

What is the breaking capacity of this MCCB at different voltages?

At 240 V it interrupts 187 kA; at 415 V and 440 V, 121 kA; at 500 V, 75.6 kA; and at 690 V, 3 kA. The applicable rating depends on your system voltage.

Does this breaker include ground-fault monitoring?

Yes, it has ground-fault monitoring via summation current formation on the L-conductor — no separate neutral CT required.

MPN
3VA2010-5JQ36-0AA0