Siemens 3VA2010-5KP32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-5KP32-0AA0 SENTRON MCCB, 100 A, 3-Pole, ETU8

MPN3VA2010-5KP32-0AA0
Active

Siemens SENTRON 3VA2, molded case circuit breaker, 3-pole, 100 A, ETU850 electronic trip unit, line protection, 187 kA at 240 V, 121 kA at 415 V, IP40 front, communication capable.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2010-5KP32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2010-5KP32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.13.5 W

Protection & Trip Unit

3VA2010-5KP32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2010-5KP32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2010-5KP32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2010-5KP32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2010-5KP32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2010-5KP32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current, built around the ETU850 electronic trip unit. It is designed for line protection in industrial distribution panels where high fault current capacity is required — 187 kA at 240 V and 121 kA at 415 V. The ETU850 trip unit provides adjustable overcurrent protection with communication capability, allowing integration into a monitored power distribution scheme. The breaker carries an insulation voltage rating of 800 V and maintains full rated current (100 A) across the entire operating temperature range from -25 °C to 70 °C without derating. At 690 V the interrupting capacity drops to 3 kA — this breaker is optimized for 240–500 V systems where its interrupting ratings are strongest. The front face carries IP40 protection; the unit is intended for enclosed panel mounting.

Sourcing and Lifecycle

Maximum power loss is 13.5 W, which should be factored into enclosure thermal calculations for panels with multiple breakers in close proximity.

Dimensions and Panel Fit

The breaker measures 105 mm wide, 181 mm high, and 86 mm deep. The 105 mm width is the standard 3-pole MCCB footprint for the SENTRON 3VA2 frame — it occupies the same panel cutout as other 3VA2 three-pole units. Depth of 86 mm leaves clearance for rear-mounted busbars or wiring ducts in a typical 600 mm deep enclosure. Storage temperature range is -40 °C to 80 °C, exceeding the operating range — relevant for site storage before installation or for panels in unconditioned spaces.

Frequently asked questions

Who supplies 3VA2010-5KP32-0AA0 and how is it quoted for volume purchases?

This breaker is sourced through independent industrial automation distribution. It is quoted to order against an RFQ — availability and current pricing are confirmed at the time of quotation. No minimum volume is implied by the listing.

What is the interrupting capacity of 3VA2010-5KP32-0AA0 at different voltages?

At 240 V it is rated 187 kA, at 415 V and 440 V it is 121 kA, at 500 V it is 75.6 kA, and at 690 V it is 3 kA. The breaker is strongest in the 240–500 V range.

Does the 3VA2010-5KP32-0AA0 support communication?

Yes, the ETU850 trip unit includes communication function, enabling integration with power monitoring systems for remote trip indication and current measurement.

MPN
3VA2010-5KP32-0AA0