Skip to main content
Siemens 3VA2010-5KP32-0AB0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-5KP32-0AB0 SENTRON MCCB, 100 A, 187 kA at 24

MPN3VA2010-5KP32-0AB0

Siemens SENTRON 3VA2010-5KP32-0AB0, molded case circuit breaker, 3-pole, 100 A continuous, 187 kA breaking capacity at 240 V AC, line protection design with communication function.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2010-5KP32-0AB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20105KP320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA11

Ratings

3VA2010-5KP32-0AB0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.13.5 W

Protection & Trip Unit

3VA2010-5KP32-0AB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2010-5KP32-0AB0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2010-5KP32-0AB0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2010-5KP32-0AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2010-5KP32-0AB0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB delivers on a real panel

The Siemens 3VA2010-5KP32-0AB0 is a 3-pole SENTRON molded case circuit breaker rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling, which simplifies the panel thermal budget. Its interrupting capacity hits 187 kA at 240 V AC, dropping to 121 kA at 415 V and 440 V, then 75.6 kA at 500 V, and 3 kA at 690 V. That 187 kA figure at 240 V means it can clear a high-fault bolted short on a 240 V distribution bus without upstream coordination headaches — useful for industrial subpanels fed by large transformers. The line-protection design targets feeder and main breaker roles, not motor branch-circuit protection. Communication function is onboard, so it can report trip status and current values to a PLC or SCADA without an add-on module.

Mounting and integration

Dimensions are 181 mm high, 105 mm wide, 86 mm deep — fits standard MCCB panel cutouts. The supplied basic switch is 3VA20105KP320AA0. Two auxiliary switches HP are included, giving status feedback without extra wiring. No undervoltage release and no ground-fault monitoring on this variant; if those are needed, you are looking at a different suffix. Operating temperature range is -25 °C to 70 °C; storage from -40 °C to 80 °C (-). Power loss at rated current is 13.5 W maximum — factor that into enclosure ventilation.

Frequently asked questions

How do I get current pricing and availability for 3VA2010-5KP32-0AB0?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time via independent distribution channels; no published price or live stock count is available on this page.

What are the key ratings of 3VA2010-5KP32-0AB0?

Continuous current is 100 A at up to 70 °C ambient. Breaking capacity is 187 kA at 240 V AC, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V. Insulation voltage is 800 V rated. It is a 3-pole line-protection MCCB with communication function and two auxiliary switches.

MPN
3VA2010-5KP32-0AB0