Skip to main content
Siemens 3VA2010-5KP32-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-5KP32-0AF0 SENTRON MCCB, 100 A, 3-Pole, 187

MPN3VA2010-5KP32-0AF0

Siemens SENTRON 3VA2010-5KP32-0AF0, 3-pole molded case circuit breaker, 100 A continuous, line protection, 187 kA interrupting at 240 V, 86 mm depth.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2010-5KP32-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20105KP320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2010-5KP32-0AF0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.13.5 W

Protection & Trip Unit

3VA2010-5KP32-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2010-5KP32-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2010-5KP32-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2010-5KP32-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2010-5KP32-0AF0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What it is and what it does

The Siemens SENTRON 3VA2010-5KP32-0AF0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. It is designed for line protection, meaning it sits at the incoming feed of a distribution panel or as the main disconnect for a branch, not for motor or generator protection. The interrupting ratings are the headline: 187 kA at 240 V AC, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V. That 187 kA figure at 240 V tells you this breaker can handle a high-fault utility feed or a transformer secondary without cascading upstream — it's sized for high-available-fault installations where a standard 65 kA or 100 kA MCCB would need a current-limiting fuse ahead of it.

What the ratings mean for your panel

The 100 A continuous rating is flat from 40 °C to 70 °C — no thermal derating curve to calculate, which simplifies panel heat-rise calculations. The insulation voltage is rated 800 V, so the breaker can be used in 480 V and 600 V class systems with margin. The 3-pole configuration handles three-phase feeds. The unit includes a trip indicator and comes with one auxiliary switch plus one trip alarm switch, so you get a remote status signal without adding a separate accessory module. Communication function is built in, meaning it can report status or be integrated into a monitoring system — useful for a facility that tracks breaker trips or load profiles. Maximum power loss is 13.5 W, which is moderate for a 100 A frame; factor that into your enclosure ventilation if you're stacking several breakers.

Physical fit and mounting

The breaker measures 181 mm high, 105 mm wide, and 86 mm deep. That 86 mm depth is the dimension that matters for enclosure depth — it fits a standard 200 mm deep panel with room for wiring gutters. The 105 mm width is the 3-pole frame width; if you're replacing a different brand's 3-pole MCCB, check that the mounting centers and bus-bar spacing match. The unit is designed for screw-mounting on a backplate or DIN-rail adapter (not included). The operating temperature range is -25 °C to 70 °C, with storage from -40 °C to 80 °C — fine for unheated warehouses or outdoor enclosures in moderate climates.

Frequently asked questions

How do I get current pricing and availability for 3VA2010-5KP32-0AF0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution. No stock or price figures are published here.

Will 3VA2010-5KP32-0AF0 drop into a panel that was specified around 3VA1110-5EF32-0AM0 without rewiring?

The 3VA2010-5KP32-0AF0 is a different frame and rating class than the 3VA1110 series. The 3VA1110 is a 160 A frame; the 3VA2010 is a 250 A frame with higher interrupting capacity. Physical dimensions and bus-bar spacing differ. You cannot assume a direct mechanical swap without verifying mounting centers and bus-bar alignment. The functional difference is that the 3VA2010 carries higher SCCR (187 kA at 240 V vs the 3VA1110's typical 65–100 kA range), so it may be specified for higher-fault locations. If your panel was built for a 3VA1110, the 3VA2010 will not fit without rework.

MPN
3VA2010-5KP32-0AF0