Siemens 3VA2010-5KP32-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2010-5KP32-0CA0 MCCB, 100 A, 3-Pole

MPN3VA2010-5KP32-0CA0

Siemens SENTRON 3VA2010-5KP32-0CA0, molded case circuit breaker, 3-pole, 100 A continuous, 187 kA breaking at 240 V, undervoltage release, communication function.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2010-5KP32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20105KP320AA0
3VA2010-5KP32-0CA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.16 W
3VA2010-5KP32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2010-5KP32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2010-5KP32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0
3VA2010-5KP32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2010-5KP32-0CA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2010-5KP32-0CA0 is a 3-pole molded case circuit breaker rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed in a warm panel. It carries a 187 kA interrupting capacity at 240 V, dropping to 121 kA at 415 V and 440 V, and 75.6 kA at 500 V.

Communication function allows integration with a BMS or energy management system via optional modules — useful for remote trip indication or load shedding.

Integration notes

The 86 mm depth, 105 mm width, and 181 mm height fit standard 3-pole MCCB footprints — verify cutout dimensions against the existing panel layout. The undervoltage release coil draws from the control circuit; confirm polarity and voltage rating before wiring. No ground-fault monitoring is built in; if GF protection is needed, pair with an external module or specify a 3VA2 variant.

Frequently asked questions

Where can I buy 3VA2010-5KP32-0CA0 and how do I get a price?

This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What are the key ratings of 3VA2010-5KP32-0CA0?

100 A continuous, 3-pole, 187 kA interrupting at 240 V, 121 kA at 415/440 V, 75.6 kA at 500 V, 3 kA at 690 V. Undervoltage release and communication function are included.

Does 3VA2010-5KP32-0CA0 include undervoltage protection?

Yes, it is equipped with an undervoltage release (UVR) that trips the breaker when control voltage drops below the dropout threshold.

What is the depth of 3VA2010-5KP32-0CA0?

The depth is 86 mm (3.39 in).

MPN
3VA2010-5KP32-0CA0