Skip to main content
Siemens 3VA2010-5KP32-0DC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-5KP32-0DC0 SENTRON MCCB, 100 A, 187 kA at 24

MPN3VA2010-5KP32-0DC0

Siemens SENTRON 3VA2 molded case circuit breaker, line protection, 3-pole, 100 A (Iu), ETU850 release, 187 kA at 240 V, with communication function and undervoltage release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2010-5KP32-0DC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2010-5KP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2010-5KP32-0DC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96.25 A
Current at 60 °C92.5 A
Current at 65 °C88.75 A
Current at 70 °C85 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V3.4 kA
Power loss, max.16 W
3VA2010-5KP32-0DC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
3VA2010-5KP32-0DC0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2010-5KP32-0DC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts2
3VA2010-5KP32-0DC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2010-5KP32-0DC0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

The Siemens 3VA2010-5KP32-0DC0 is a SENTRON 3VA2 molded case circuit breaker rated for 100 A continuous current (Iu) at 40 °C, with the ETU850 electronic trip unit providing adjustable overload and short-circuit protection curves. The 187 kA breaking capacity at 240 V drops to 121 kA at 415 V and 440 V, then to 79 kA at 500 V, and 3.4 kA at 690 V — the SCCR headroom at typical 400 V distribution voltages means this breaker clears high-fault scenarios without cascading upstream, which matters for selective coordination studies on a main or feeder position. The 100 A rating holds flat through 50 °C, then derates linearly to 85 A at 70 °C — a panel builder stacking breakers in a warm enclosure should account for that thermal curve rather than assuming the full 100 A at the ambient the cabinet actually sees.

At 105 mm wide, 181 mm tall, and 86 mm deep, this 3-pole MCCB fits the standard SENTRON 3VA2 mounting footprint. The depth of 86 mm is the dimension that governs gland-plate clearance in a shallow backpanel — verify the enclosure depth allows for rear connection access and the undervoltage release (UVR) module that ships with this variant. The auxiliary contact version carries 2 HQ switches, and the integrated auxiliary trip is order code 3VA9608-0BB25. The supplied basic switch is 3VA2010-5KP32-0AA0 — these are the factory-matched accessories, not field-retrofit options.

The ETU850 release supports communication function and other measurement functions, which means this breaker can report load data and event logs over the integrated comms interface — useful for a panel that feeds into a building management or power monitoring system without a separate metering module.

Thermal and electrical endurance

For motor-switching or frequent ON/OFF cycles, derate per the manufacturer's electrical endurance curve (not in this evidence set). Power loss is 16 W maximum at rated current, which contributes to the enclosure heat load calculation.

Frequently asked questions

How do I get current pricing and availability for 3VA2010-5KP32-0DC0?

This part is sourced and quoted to order against an RFQ through independent distribution; current pricing and availability are confirmed at quote time.

What is the breaking capacity of 3VA2010-5KP32-0DC0 at 415 V?

The breaking capacity at 415 V is 121 kA, matching the rating at 440 V. At 240 V it is 187 kA, at 500 V it is 79 kA, and at 690 V it is 3.4 kA.

What trip unit does 3VA2010-5KP32-0DC0 use?

It uses the ETU850 electronic overcurrent release, which provides adjustable protection curves and supports communication and other measurement functions.

MPN
3VA2010-5KP32-0DC0