Skip to main content
Siemens 3VA2010-6HL32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-6HL32-0AH0 SENTRON MCCB, 100 A, 3-Pole, 242

MPN3VA2010-6HL32-0AH0

Siemens SENTRON 3VA2010-6HL32-0AH0, molded case circuit breaker, 3-pole, 100 A rated continuous current, 242 kA breaking capacity at 240 V, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2010-6HL32-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20106HL320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2010-6HL32-0AH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3 kA
Power loss, max.13.5 W

Protection & Trip Unit

3VA2010-6HL32-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2010-6HL32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2010-6HL32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2010-6HL32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2010-6HL32-0AH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB does and where it fits

The Siemens 3VA2010-6HL32-0AH0 is a SENTRON molded case circuit breaker (MCCB) rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Its 242 kA breaking capacity at 240 V AC handles high-fault utility feeds, while the 3 kA at 690 V covers the low end for lightly loaded industrial lines. The 3-pole form factor with a trip indicator and two auxiliary switches plus one trip alarm switch (HQ) gives you remote status feedback without an add-on module. Panel builders: the 86 mm depth and 105 mm width fit standard MCCB mounting footprints; the 181 mm height clears most enclosure gland plates.

Breaking capacity and selectivity headroom

At 415 V and 440 V the breaker holds 187 kA — identical performance at both levels, which simplifies coordination studies for 400 V-class distribution. The 121 kA at 500 V still covers most industrial step-down transformers. That 3 kA at 690 V looks low, but 690 V applications typically use dedicated high-voltage breakers; this MCCB is sized for the 240–500 V sweet spot where fault currents run high.

Integration and environmental limits

Rated insulation voltage is 800 V. Operating temperature range -25 °C to 70 °C, storage from -40 °C to 80 °C. Maximum power loss 13.5 W. No undervoltage release, no ground-fault monitoring, no communication function.

Frequently asked questions

What is 3VA2010-6HL32-0AH0's listed depth?

The depth is 86 mm (3.39 in), width 105 mm (4.13 in), height 181 mm (7.13 in).

MPN