The 3VA2010-6HL32-0BA0: The interrupting capacity is substantial: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 4 kA at 690 V. This SCCR headroom means it can be applied in high-fault-capacity industrial panels without cascading upstream.
This thermal curve is critical for panel builders calculating fill factor and heat rise inside the enclosure. Dimensions are 181 mm height, 105 mm width, and 86 mm depth. Maximum power loss is 16 W at rated current — a modest figure that simplifies thermal management in a sealed enclosure.
Release and compliance
The UVR ensures the breaker trips on loss of control voltage — a standard requirement for safety circuits and emergency-stop chains. The part carries no auxiliary contact version or communication function — it is a standalone line-protection device.