Skip to main content
Siemens 3VA2010-6HL32-0BC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-6HL32-0BC0 MCCB, 100 A, 3-Pole, 242 kA at 24

MPN3VA2010-6HL32-0BC0

Siemens SENTRON 3VA2010-6HL32-0BC0, molded case circuit breaker, 3-pole, 100 A continuous, line protection, with undervoltage release and 2 auxiliary switches HQ.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2010-6HL32-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20106HL320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2010-6HL32-0BC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3 kA
Power loss, max.16 W

Protection & Trip Unit

3VA2010-6HL32-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2010-6HL32-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2010-6HL32-0BC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2010-6HL32-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2010-6HL32-0BC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB carries and where it fits

The Siemens SENTRON 3VA2010-6HL32-0BC0 is a 3-pole molded case circuit breaker rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Interrupting capacity hits 242 kA at 240 V, dropping to 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V. That SCCR headroom makes it a strong choice for high-fault distribution panels where selectivity with upstream breakers is critical. Designed for line protection, this MCCB includes an undervoltage release (UVR) and two factory-fitted HQ auxiliary switches — no field retrofitting needed for those functions. The UVR ensures the breaker trips on loss of control voltage, a common requirement in safety circuits and emergency-stop chains.

Physical fit and panel integration

Dimensions: 86 mm deep, 105 mm wide, 181 mm tall. That footprint matches the standard SENTRON 3VA fixed-mount MCCB form factor — direct swap into existing 3VA panel cutouts without re-drilling. The width is the critical dimension for multi-breaker groupings on a DIN rail or mounting plate.

What the ratings mean for your application

The 100 A continuous rating is flat across the operating temperature range of -25 °C to 70 °C, so you don't lose capacity in a warm enclosure. Power loss is 16 W maximum — manageable for thermal budgeting in a dense panel. The interrupting ratings (242 kA at 240 V, 187 kA at 415/440 V, 121 kA at 500 V, 3 kA at 690 V) tell you this breaker can clear high fault currents without cascading upstream. For a 480 V distribution board with a transformer secondary fault current of 65 kA, this breaker has nearly 3× headroom — that's selectivity margin.

Frequently asked questions

Will 3VA2010-6HL32-0BC0 drop into a panel specified around 5SQ2370-2YA05 without rewiring?

The 3VA series uses a different mounting footprint and terminal layout than the 5SQ series. Physical fit is not guaranteed — verify the cutout dimensions and bus bar spacing before ordering. The 3VA is a current-production design; the 5SQ is an older platform.

MPN
3VA2010-6HL32-0BC0