Skip to main content
Siemens 3VA2010-6HL32-0CL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-6HL32-0CL0 MCCB 100A, 242kA at 240V

MPN3VA2010-6HL32-0CL0

Siemens SENTRON 3VA2010-6HL32-0CL0, molded case circuit breaker, 3-pole, 100 A, 242 kA at 240 V, line protection, ETU320 release, with undervoltage release and auxiliary switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2010-6HL32-0CL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2010-6HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2010-6HL32-0CL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96.25 A
Current at 60 °C92.5 A
Current at 65 °C88.75 A
Current at 70 °C85 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V4 kA
Power loss, max.16 W
3VA2010-6HL32-0CL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2010-6HL32-0CL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2010-6HL32-0CL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA2010-6HL32-0CL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2010-6HL32-0CL0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

The Siemens SENTRON 3VA2010-6HL32-0CL0 is a 3-pole molded case circuit breaker rated for 100 A continuous current, built for line protection duty. At 415 V it still breaks 187 kA, so it's sized for high-fault panels feeding motor control centers or distribution boards where the utility transformer is close.

The 100 A rating holds flat from 40 °C to 50 °C — no derating needed in a warm panel. It starts stepping down at 55 °C: 96.25 A, then 92.5 A at 60 °C, 88.75 A at 65 °C, and 85 A at 70 °C. If your enclosure runs hot, that derating curve is what tells you whether this frame size works or you need to bump up. The rated insulation voltage is 800 V, so it's comfortable in 480 V and 600 V systems with headroom. It's a straight line-protection device: overcurrent and short-circuit only. The auxiliary contact block includes 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ type), so you get status feedback for a PLC or alarm panel without adding a separate module.

Panel integration

Dimensions: 105 mm wide, 181 mm tall, 86 mm deep — fits a 3-pole MCCB footprint common across the SENTRON 3VA family. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C.

Frequently asked questions

Where can I buy 3VA2010-6HL32-0CL0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of this MCCB?

242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 4 kA at 690 V.

What trip unit does this breaker use?

It uses an ETU320 electronic trip unit — line protection only, no communication or voltage trigger.

What auxiliary contacts are included?

2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ type).

MPN