Skip to main content
Siemens 3VA2010-6HN32-0CL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-6HN32-0CL0 SENTRON MCCB, 100 A, 3-Pole, 242

MPN3VA2010-6HN32-0CL0

Siemens SENTRON 3VA2010-6HN32-0CL0, molded case circuit breaker, 3-pole, 100 A continuous rating, 242 kA interrupting at 240 V, line protection design with undervoltage release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2010-6HN32-0CL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20106HN320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2010-6HN32-0CL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3 kA
Power loss, max.16 W

Protection & Trip Unit

3VA2010-6HN32-0CL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2010-6HN32-0CL0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2010-6HN32-0CL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2010-6HN32-0CL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2010-6HN32-0CL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this 100 A MCCB delivers on the line

The Siemens 3VA2010-6HN32-0CL0 is a SENTRON molded case circuit breaker rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed as the panel warms up near the top of the enclosure. Three-pole design with a trip indicator and an undervoltage release (UVR) built in. A voltage dip on the control supply drops the breaker open. Interrupting capacity hits 242 kA at 240 V and still 187 kA at 415 V, meaning it can sit at the main distribution point in a high-fault plant without needing a current-limiting upstream breaker.

Panel fit and footprint

Dimensions are 105 mm wide, 181 mm tall, 86 mm deep — a standard SENTRON 3VA2 frame that bolts into a panel on a mounting plate or DIN-rail adapter. The 86 mm depth leaves room behind the gland plate for cable bends. Auxiliary switch complement is two auxiliary switches plus one trip alarm and one electrical alarm switch (HQ design), so the PLC gets a dedicated fault signal without sharing contacts. Maximum power loss of 16 W at rated load keeps the internal enclosure temperature rise manageable — factor it into your thermal budget if the breaker shares a compartment with drives.

MPN
3VA2010-6HN32-0CL0