Specifications

3VA2010-6HN32-0JC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20106HN320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2010-6HN32-0JC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3 kA
Power loss, max.13.5 W
3VA2010-6HN32-0JC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2010-6HN32-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2010-6HN32-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA2010-6HN32-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2010-6HN32-0JC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

It carries a 242 kA interrupting capacity at 240 V AC, dropping to 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V — so the SCCR headroom is substantial at typical 480 V industrial feeds, but you need to check coordination at the 690 V end if that's your line voltage.

Sizing and thermal performance

That's unusual for an MCCB; most start tapering above 40 °C. Maximum power loss is 13.5 W, which is modest for a 100 A frame and keeps the enclosure heat rise manageable.

The shunt trip and auxiliary switches are factory-integrated, so no field-add kit to lose or miswire.

Frequently asked questions

Does this breaker include a shunt trip?

Yes, the design includes a shunt trip (STL) auxiliary release for remote tripping, plus two HQ auxiliary switches for status indication.

MPN
3VA2010-6HN32-0JC0