The Siemens SENTRON 3VA2010-6HN32-0KL0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Its breaking capacity is 242 kA at 240 V, 187 kA at 415 V and 440 V, and 121 kA at 500 V, dropping to 3 kA at 690 V. Designed for line protection, this MCCB carries a shunt trip release (STL) and a complement of auxiliary switches: two auxiliary switches, one trip alarm switch, and one electrical alarm switch (HQ designation). The trip indicator and voltage trigger are present; undervoltage release and ground-fault monitoring are not fitted on this variant. Panel integration is straightforward — the 105 mm width, 181 mm height, and 86 mm depth fit standard SENTRON 3VA mounting footprints. Maximum power loss is 13.5 W, so thermal budgeting inside the enclosure is manageable.

Siemens SENTRON 3VA2010-6HN32-0KL0 MCCB, 100 A, 3-Pole, 242
Siemens SENTRON 3VA series molded case circuit breaker, 3VA2010-6HN32-0KL0, 100 A continuous, 3-pole, 242 kA breaking capacity at 240 V, line protection design.
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Basic switch (supplied) ref. | 3VA20106HN320AA0 |
| Integrated auxiliary / alarm switch ref. | 3VA9988-0AB22 |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 100 A |
| Current at 45 °C | 100 A |
| Current at 50 °C | 100 A |
| Current at 55 °C | 100 A |
| Current at 60 °C | 100 A |
| Current at 65 °C | 100 A |
| Current at 70 °C | 100 A |
| Switching capacity class | H |
| Breaking capacity at 240 V | 242 kA |
| Breaking capacity at 415 V | 187 kA |
| Breaking capacity at 440 V | 187 kA |
| Breaking capacity at 500 V | 121 kA |
| Breaking capacity at 690 V | 3 kA |
| Power loss, max. | 13.5 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | ETU350 |
| Overcurrent protection function | LSI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | on both sides nut keeper kit |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | Yes |
| Trip indicator | Yes |
| Communication function | No |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 4 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 25 000 |
| Height | 181 mm |
| Width | 105 mm |
| Depth | 86 mm |
| Height (in) | 7.13 in |
| Width (in) | 4.13 in |
| Depth (in) | 3.39 in |
Product details
Frequently asked questions
What is the breaking capacity of this MCCB at 415 V?
187 kA at 415 V, which is the same rating as at 440 V. At 240 V it reaches 242 kA.
How do I get current pricing and availability for 3VA2010-6HN32-0KL0?
Submit an RFQ through this listing — availability and current pricing are confirmed at quote time through independent distribution channels.
Does this MCCB include a shunt trip release?
Yes, it is fitted with a shunt trip (STL) release, plus two auxiliary switches, one trip alarm switch, and one electrical alarm switch.