Skip to main content
Siemens 3VA2010-6HN36-0JL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-6HN36-0JL0 SENTRON MCCB, 100 A, 3-Pole, ETU3

MPN3VA2010-6HN36-0JL0

Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2010-6HN36-0JL0, 3-pole, 100 A, line protection, ETU350 electronic trip unit, shunt trip (STL), 2 aux + 1 trip alarm + 1 electrical alarm HQ.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2010-6HN36-0JL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2010-6HN36-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2010-6HN36-0JL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96.25 A
Current at 60 °C92.5 A
Current at 65 °C88.75 A
Current at 70 °C85 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V4 kA
Power loss, max.13.5 W
3VA2010-6HN36-0JL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2010-6HN36-0JL0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2010-6HN36-0JL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA2010-6HN36-0JL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2010-6HN36-0JL0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

The 3VA2010-6HN36-0JL0: This MCCB delivers 242 kA interrupting rating at 240 V, dropping to 187 kA at 415 V and 440 V, then 121 kA at 500 V, and 4 kA at 690 V. The 4 kA at 690 V still covers most industrial 690 V distribution, but selectivity studies at that voltage need the lower ceiling.

Trip unit and auxiliary contacts

The ETU350 electronic trip unit provides LSI protection (long-time, short-time, instantaneous) with adjustable settings. A shunt trip (STL) release is built in for remote tripping.

Thermal derating and environment

Rated 100 A from 40 °C through 50 °C, then derates linearly to 85 A at 70 °C. Maximum power loss is 13.5 W.

Frequently asked questions

What is the interrupting rating of 3VA2010-6HN36-0JL0 at 240 V?

242 kA at 240 V. That is the highest interrupting rating in its voltage range, suitable for high-fault service entrance applications.

What trip unit does this MCCB use?

The ETU350 electronic trip unit with LSI protection (long-time, short-time, instantaneous). It also has a built-in shunt trip (STL) for remote tripping.

Where can I buy 3VA2010-6HN36-0JL0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
3VA2010-6HN36-0JL0