Skip to main content
Siemens 3VA2010-6HN36-0KL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-6HN36-0KL0 SENTRON MCCB, 100 A, 3-Pole, 242

MPN3VA2010-6HN36-0KL0

Siemens SENTRON 3VA series, molded case circuit breaker (MCCB), 3VA2010-6HN36-0KL0, 100 A rated continuous current, 3-pole, line protection design, interrupting capacity 242 kA at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2010-6HN36-0KL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20106HN360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2010-6HN36-0KL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3 kA
Power loss, max.13.5 W
3VA2010-6HN36-0KL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2010-6HN36-0KL0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2010-6HN36-0KL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA2010-6HN36-0KL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2010-6HN36-0KL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2010-6HN36-0KL0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current at 40 °C, designed for line protection in distribution panels and motor control centers. Its interrupting capacity reaches 242 kA at 240 V AC, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V — figures that define its fault-clearing capability across common industrial voltage tiers.

The 100 A continuous rating holds flat across the full ambient range from 40 °C to 70 °C — no derating needed up to the maximum operating temperature, which simplifies panel thermal budgeting. At 690 V the capacity drops to 3 kA, so verify the available fault current at the point of installation for 690 V systems. Physical fit: 86 mm deep, 105 mm wide, 181 mm high. The 3-pole, 100 A frame mounts in standard panel cutouts for SENTRON 3VA fixed breakers. The trip indicator and voltage trigger are present on the front face for visual status.

Frequently asked questions

What is the interrupting capacity of this MCCB at different voltages?

The interrupting capacity is 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V. These values define the maximum fault current the breaker can safely clear at each voltage level.

How do I get current pricing and availability for 3VA2010-6HN36-0KL0?

Submit an RFQ through the storefront. Pricing and stock levels are confirmed at quote time — the part is sourced to order through independent distribution channels.

MPN
3VA2010-6HN36-0KL0