Breaking capacity reaches 242 kA at 240 V and 187 kA at 415 V, so it clears high-fault conditions without cascading upstream — sized for a main breaker position in a 480 V panel feeding multiple motor loads.
Panel footprint and integration
At 13.5 W maximum power loss, the heat it dumps into the cabinet is modest — no forced cooling needed for a single unit, but group several breakers and check the enclosure's thermal budget.