Skip to main content
Siemens 3VA2010-7JP32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-7JP32-0AA0 SENTRON MCCB, 100 A, 3-Pole, ETU5

MPN3VA2010-7JP32-0AA0
Active

Siemens SENTRON 3VA2010-7JP32-0AA0, molded case circuit breaker, 3-pole, 100 A continuous, ETU550 electronic trip unit, 330 kA at 240 V, line protection design with communication function.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2010-7JP32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2010-7JP32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3 kA
Power loss, max.7.7 W

Protection & Trip Unit

3VA2010-7JP32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2010-7JP32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2010-7JP32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2010-7JP32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2010-7JP32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Siemens SENTRON 3VA2010-7JP32-0AA0 — 100 A MCCB with ETU550 Trip Unit

The Siemens SENTRON 3VA2010-7JP32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current, designed for line protection in distribution panels and switchgear assemblies. It carries the ETU550 electronic trip unit, which provides adjustable overload and short-circuit protection curves — a step up from fixed thermal-magnetic breakers for selectivity coordination studies. Breaking capacity reaches 330 kA at 240 V AC, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3 kA at 690 V. That 330 kA at 240 V is the headline number for high-fault service-entrance applications; the 242 kA at 415 V still covers most industrial distribution scenarios. The 690 V rating drops sharply to 3 kA — this breaker is not the primary choice for 690 V motor circuits unless fault current is tightly limited upstream. Rated insulation voltage is 800 V, and the unit includes a communication function for integration with higher-level monitoring or energy management systems — useful for facilities tracking branch-circuit load data without adding separate metering.

Sizing and Thermal Performance

The 100 A rating holds flat across the entire operating temperature range from -25 °C to 70 °C — no derating needed up to the maximum ambient. That simplifies panel sizing in unconditioned enclosures or near heat-producing equipment. Power loss at rated current is 7.7 W maximum, manageable for standard enclosure thermal calculations. Dimensions are 181 mm height, 105 mm width, 86 mm depth — a standard SENTRON 3VA frame footprint. The IP40 front protection means it is suitable for enclosed panel mounting where the breaker face is behind a closed door; not rated for washdown or outdoor exposure without an additional enclosure.

Frequently asked questions

What trip unit does the 3VA2010-7JP32-0AA0 use?

It uses the ETU550 electronic trip unit, which provides adjustable overload and short-circuit protection curves for selectivity coordination.

MPN
3VA2010-7JP32-0AA0