Skip to main content
Siemens 3VA2010-7JQ32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2010-7JQ32-0AA0 MCCB, 100 A, 330 kA at 24

MPN3VA2010-7JQ32-0AA0
Active

Siemens SENTRON 3VA2010-7JQ32-0AA0, molded case circuit breaker, 3-pole, 100 A, ETU560 electronic trip unit, breaking capacity 330 kA at 240 V, 242 kA at 415 V, 86 mm depth, 105 mm width, 181 mm height.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2010-7JQ32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2010-7JQ32-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3 kA
Power loss, max.13.5 W
3VA2010-7JQ32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
3VA2010-7JQ32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2010-7JQ32-0AA0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2010-7JQ32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2010-7JQ32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.1 in
Width (in)4.1 in
Depth (in)3.4 in

Product details

The Siemens SENTRON 3VA2010-7JQ32-0AA0 is a 3-pole molded case circuit breaker rated a full 100 A continuously from 40 °C through 70 °C — no derating curve to chase across the panel ambient range. Breaking capacity hits 330 kA at 240 V and 242 kA at both 415 V and 440 V, then drops to 187 kA at 500 V and 3 kA at 690 V. The ETU560 electronic trip unit gives adjustable long-time pickup (Ig) from 0.8 s to 100 A and short-time pickup (Ii) from 150 A to 1200 A, so you set the coordination curve to the load, not the other way around.

Communication function is built in, so it can talk to a higher-level controller or energy management system over the SENTRON bus; no separate comm module to buy and mount.

Frequently asked questions

Where can I buy 3VA2010-7JQ32-0AA0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote (RFQ) with your quantity and target delivery window; availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA2010-7JQ32-0AA0 at 415 V?

242 kA at 415 V. The same rating applies at 440 V. At 240 V it reaches 330 kA, and at 500 V it drops to 187 kA.

What trip unit does this MCCB use?

The ETU560 electronic trip unit. It provides adjustable long-time pickup (Ig) from 0.8 s to 100 A and short-time pickup (Ii) from 150 A to 1200 A.

MPN
3VA2010-7JQ32-0AA0