Skip to main content
Siemens 3VA2010-7KP36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2010-7KP36-0AA0 MCCB, 100 A, 3-Pole, ETU8

MPN3VA2010-7KP36-0AA0
Active

Siemens SENTRON 3VA2010-7KP36-0AA0, molded case circuit breaker, 3-pole, 100 A, ETU850 electronic trip unit, 330 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2010-7KP36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2010-7KP36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3 kA
Power loss, max.7.7 W

Protection & Trip Unit

3VA2010-7KP36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2010-7KP36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2010-7KP36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2010-7KP36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2010-7KP36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this breaker is and what it does

The Siemens SENTRON 3VA2010-7KP36-0AA0 is a 3-pole molded case circuit breaker rated for 100 A continuous current, designed for line protection. It carries an ETU850 electronic trip unit. Insulation voltage is rated 800 V. Breaking capacity is 330 kA at 240 V, tapering to 242 kA at 415/440 V, 187 kA at 500 V, and 3 kA at 690 V. At 415 V, that 242 kA SCCR handles high-fault utility feeds without cascading upstream — you can size the main breaker for full selectivity, not just series rating. The 3 kA at 690 V is a low-end figure; this is not a 690 V main breaker for high-fault installations. The breaker includes a communication function and other measurement functions.

Physical fit and panel integration

Dimensions: 181 mm height, 105 mm width, 86 mm depth. That width is the standard 105 mm for a 3-pole SENTRON 3VA frame — it mounts on the DIN rail or directly to the panel backplate with the same footprint as the 3VA1 family. The IP40 front protection means it is splash-resistant from the front but not sealed; install it inside a dead-front enclosure rated for the environment. No undervoltage release and no voltage trigger on this variant — if you need UVR or shunt trip for emergency-off circuits, you order a different suffix. The trip indicator is also absent, so you rely on the ETU850's local LED or the communication interface for trip status.

MPN