Skip to main content
Siemens 3VA2010-7KP46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-7KP46-0AA0 SENTRON MCCB, 100A, 4-Pole, ETU85

MPN3VA2010-7KP46-0AA0
Active

Siemens SENTRON 3VA2, molded case circuit breaker, 4-pole, 100 A, ETU850 electronic trip unit, line protection, 330 kA at 240 V, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2010-7KP46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2010-7KP46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classC
Breaking capacity at 240 V330 kA
Breaking capacity at 415 V242 kA
Breaking capacity at 440 V242 kA
Breaking capacity at 500 V187 kA
Breaking capacity at 690 V3 kA
Power loss, max.7.7 W

Protection & Trip Unit

3VA2010-7KP46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2010-7KP46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2010-7KP46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2010-7KP46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2010-7KP46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

What this 4-pole 100 A MCCB carries

The Siemens SENTRON 3VA2010-7KP46-0AA0 is a 4-pole molded case circuit breaker rated for 100 A continuous at 40 °C through 70 °C — no derating needed across that band, which simplifies panel schedules in warm enclosures. The ETU850 electronic trip unit handles line protection duty with communication and measurement functions onboard, so it reports current draw and trip events back to the control system without a separate metering module. Breaking capacity hits 330 kA at 240 V and 242 kA at 415 V, giving solid SCCR headroom for high-fault industrial services.

Mounting and panel fit

The breaker measures 140 mm wide by 181 mm tall by 86 mm deep — a standard SENTRON 3VA2 footprint that drops into existing MCCB panel cutouts without re-drilling gland plates. IP40 on the front face means it's protected against solid objects over 1 mm but not sealed against moisture; keep it inside the enclosure, not on a washdown wall.

Frequently asked questions

Where can I buy 3VA2010-7KP46-0AA0 and what is the lead time?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number published here.

What is the closest functional second-source for 3VA2010-7KP46-0AA0?

The peer 3VA2110-8HN32-0AA0 shares the same 4-pole, 100 A frame and ETU850 trip platform, but it carries a different breaking capacity curve and accessory configuration. Verify the SCCR requirements and auxiliary contact count before substituting — the footprint is the same, but the protection coordination may shift.

MPN
3VA2010-7KP46-0AA0