What this 4-pole 100 A MCCB carries
The Siemens SENTRON 3VA2010-7KP46-0AA0 is a 4-pole molded case circuit breaker rated for 100 A continuous at 40 °C through 70 °C — no derating needed across that band, which simplifies panel schedules in warm enclosures. The ETU850 electronic trip unit handles line protection duty with communication and measurement functions onboard, so it reports current draw and trip events back to the control system without a separate metering module. Breaking capacity hits 330 kA at 240 V and 242 kA at 415 V, giving solid SCCR headroom for high-fault industrial services.
Mounting and panel fit
The breaker measures 140 mm wide by 181 mm tall by 86 mm deep — a standard SENTRON 3VA2 footprint that drops into existing MCCB panel cutouts without re-drilling gland plates. IP40 on the front face means it's protected against solid objects over 1 mm but not sealed against moisture; keep it inside the enclosure, not on a washdown wall.