Skip to main content
Siemens 3VA2010-8HL46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-8HL46-0AA0 SENTRON MCCB, 100 A, 4-Pole, ETU3

MPN3VA2010-8HL46-0AA0
Active

Siemens SENTRON 3VA2010-8HL46-0AA0, molded case circuit breaker, 4-pole, 100 A, ETU320 electronic trip unit, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2010-8HL46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2010-8HL46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.7.7 W

Protection & Trip Unit

3VA2010-8HL46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2010-8HL46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2010-8HL46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2010-8HL46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2010-8HL46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

MCCB for line protection with ETU320 trip unit

The Siemens 3VA2010-8HL46-0AA0 is a SENTRON molded case circuit breaker (MCCB) rated for 100 A continuous current across the full ambient temperature range from 40 °C to 70 °C — no derating needed up to that ceiling. Its four-pole design and electronic ETU320 overcurrent release make it a fit for line protection in distribution panels where selectivity and adjustable trip curves are required. Breaking capacity reaches 440 kA at 240 V AC, stepping to 330 kA at 415/440 V, 220 kA at 500 V, and 52.5 kA at 690 V. That SCCR headroom covers most industrial service-entrance and feeder applications without needing a current-limiting fuse upstream.

Integration notes

Dimensions are 181 mm high, 140 mm wide, and 86 mm deep — a standard SENTRON 3VA footprint that fits existing panel layouts. Front-side IP40 protection covers the operator interface; the breaker is designed for line protection without undervoltage release or communication functions, so it's a straightforward replacement in a distribution board.

Frequently asked questions

Where can I buy 3VA2010-8HL46-0AA0 and get current pricing?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position.

What is the breaking capacity of this MCCB at different voltages?

Rated breaking capacity is 440 kA at 240 V, 330 kA at 415 V and 440 V, 220 kA at 500 V, and 52.5 kA at 690 V.

Does this breaker require derating at elevated ambient temperatures?

No derating needed — the 100 A continuous rating holds across the full 40 °C to 70 °C ambient range.

MPN
3VA2010-8HL46-0AA0