Skip to main content
Siemens 3VA2010-8JP36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2010-8JP36-0AA0 SENTRON MCCB, 100 A, 3-Pole, ETU5

MPN3VA2010-8JP36-0AA0
Active

Siemens SENTRON 3VA series, Molded case circuit breaker, 3VA2010-8JP36-0AA0, 3-pole, 100 A, ETU550 electronic trip unit, line protection, 440 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2010-8JP36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2010-8JP36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C100 A
Current at 70 °C100 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.7.7 W

Protection & Trip Unit

3VA2010-8JP36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2010-8JP36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2010-8JP36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2010-8JP36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2010-8JP36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB is, and what the ratings mean for your panel

The Siemens 3VA2010-8JP36-0AA0 is a SENTRON molded case circuit breaker (MCCB) designed for line protection in distribution panels. It carries a continuous current rating of 100 A across the full ambient temperature range from 40 °C to 70 °C — no derating needed up to that ceiling, which simplifies panel thermal budgeting when the breaker sits next to other heat sources. The ETU550 electronic trip unit gives you adjustable long-time, short-time, instantaneous, and ground-fault protection curves. That matters for selectivity coordination downstream — you can shape the trip response to keep a branch fault from taking out the whole feeder. The communication function onboard means this breaker can report status and trip events to a higher-level control system, which is useful for remote monitoring or predictive maintenance on a critical line. Breaking capacity is the headline spec for an MCCB: this one delivers 440 kA at 240 V, 330 kA at 415 V and 440 V, 220 kA at 500 V, and 52.5 kA at 690 V. Those numbers tell you it can safely interrupt a fault at the available short-circuit current of your panel's transformer or upstream feed — if your plant's service entrance can deliver 200 kA at 480 V, this breaker handles it. The 800 V rated insulation voltage confirms it's rated for 690 V nominal systems with margin. The 3-pole construction suits three-phase feeders. Front-side IP40 protection means tools or fingers won't contact live parts from the front, but the breaker is not sealed against dust ingress — it belongs inside an enclosure, not in a washdown area.

Panel fit and footprint

The breaker measures 86 mm deep × 105 mm wide × 181 mm high. That 105 mm width is the standard 3-pole MCCB footprint for the 3VA frame size — it occupies one 105 mm-wide slot on the DIN rail or mounting plate. Depth of 86 mm means it clears most standard 200 mm-deep enclosures with room for wiring gutters. If you are replacing an older 3VA1 frame breaker, check the mounting hole pattern; the 3VA2 frame shares the same 105 mm width but verify the depth clearance against your existing backpanel.

Frequently asked questions

Where can I buy 3VA2010-8JP36-0AA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent industrial distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, not listed here.

What is the closest functional second-source to 3VA2010-8JP36-0AA0?

The 3VA1110-5EF32-0AM0 is a different frame size (3VA1 vs 3VA2) with a different trip unit (ETU320 vs ETU550). The 3VA2 frame carries higher breaking capacities and the ETU550 offers more adjustable protection curves. They are not drop-in replacements — the mounting footprint and wiring scheme differ.

Will 3VA2010-8JP36-0AA0 drop into a panel specified around 3VA1110-5EF32-0AM0 without rewiring?

No. The 3VA2 frame (this part) is physically larger than the 3VA1 frame. The width is the same 105 mm, but depth and height differ. The terminal arrangements and lug sizes may also differ. Panel modification and re-termination would be required.

What compliance documentation does this breaker carry?

The SENTRON 3VA series carries IEC/EN 60947-2 certification for molded case circuit breakers. UL and CSA listings are standard for the North American market variants. RoHS and REACH compliance documentation is available from Siemens upon request.

MPN