Skip to main content
Siemens 3VA2025-6JQ42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2025-6JQ42-0AA0 SENTRON MCCB, 4P, 25A, 242kA at 2

MPN3VA2025-6JQ42-0AA0
Active

Siemens SENTRON 3VA2025-6JQ42-0AA0, 4-pole molded case circuit breaker, 25 A, interrupting capacity 242 kA at 240 V, ETU560 release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2025-6JQ42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2025-6JQ42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C25 A
Current at 60 °C25 A
Current at 65 °C25 A
Current at 70 °C25 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3 kA
Power loss, max.0.84 W

Protection & Trip Unit

3VA2025-6JQ42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU560
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L + N conductor

Construction & Connection

3VA2025-6JQ42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2025-6JQ42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2025-6JQ42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2025-6JQ42-0AA0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

What this MCCB does and where it lands

The Siemens SENTRON 3VA2025-6JQ42-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 25 A flat across the full operating temperature range from 40 °C to 70 °C — no derating needed up to the 70 °C ceiling. Its interrupting capacity hits 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V, so it handles high-fault scenarios typical in industrial distribution without cascading upstream. It's equipped with the ETU560 electronic trip unit, which gives adjustable N-conductor protection (OFF, 40 % to 160 % of Iu) and ground-fault monitoring via summation current formation on L + N. The unit communicates — the communication function is built in — so it can talk to a higher-level control system for status and metering without an add-on module. The 86 mm depth, 140 mm width, and 181 mm height fit the standard SENTRON panel footprint. IP40 on the front means it's protected against solid objects over 1 mm but not sealed against moisture — fine for a dry indoor cabinet, not for washdown zones.

Lifecycle and sourcing reality

For a BOM freeze or a new panel design, this part is a safe drop-in today. No LTB clock is ticking. The ETU560 release and communication function mean it's ready for modern switchgear that needs remote monitoring or selective coordination studies.

What the ratings mean for your panel

The 25 A rating is a true thermal-magnetic continuous current — no temperature derating from 40 °C to 70 °C, which simplifies panel thermal calculations. If your cabinet ambient stays under 70 °C, you get the full 25 A per pole. The interrupting capacity at 415 V (187 kA) is typical for a high-fault industrial service entrance or a large sub-distribution board. At 690 V it drops to 3 kA — that's still enough for most motor control center (MCC) applications at that voltage, but verify your available fault current if you're feeding a 690 V drive. Rated insulation voltage Ui is 800 V, so the breaker is insulated for 690 V systems with margin. The IP40 front is standard for a panel-mounted device; the enclosure provides the rest of the ingress protection.

Compliance and documentation

The reference code per IEC 81346-2 is Q, which is the standard designation for switching devices in power circuits. The unit is designed to meet IEC 60947-2 for MCCBs. For specific compliance documents (RoHS, REACH, UL file number), the manufacturer provides declarations on request — the part carries the CE mark and is listed for the European market.

Frequently asked questions

Where can I buy 3VA2025-6JQ42-0AA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — send your quantity and target delivery window for a firm offer.

What is the interrupting capacity of 3VA2025-6JQ42-0AA0 at 415 V?

At 415 V the interrupting capacity is 187 kA. At 240 V it is 242 kA, at 440 V it is 187 kA, at 500 V it is 121 kA, and at 690 V it is 3 kA.

Does 3VA2025-6JQ42-0AA0 have a communication function?

Yes, the communication function is built in. The ETU560 trip unit can communicate status and metering data to a higher-level control system without an external module.

MPN
3VA2025-6JQ42-0AA0