Breaking capacity and trip unit
The 3VA2025-7JP36-0AA0: Breaking capacity reaches 330 kA at 240 V AC, dropping to 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3 kA at 690 V. At 25 A continuous rating, this MCCB handles fault currents well above what most distribution panels can deliver — the 330 kA figure at 240 V means it safely interrupts a high-energy fault without cascading upstream. The ETU550 is a programmable electronic trip unit; combined with the communication function, it enables integration into a digital power monitoring scheme.
Panel fit and environment
Dimensions: 181 mm high, 105 mm wide, 86 mm deep. 3-pole footprint. IP40 front protection.
Sourcing and lifecycle
Lifecycle status is current. The part is sourced and quoted to order against an RFQ through independent distribution.