Skip to main content
Siemens 3VA2025-8HN46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2025-8HN46-0AA0 MCCB, 25 A, 4-Pole, ETU35

MPN3VA2025-8HN46-0AA0
Active

Siemens SENTRON 3VA series molded case circuit breaker, 3VA2025-8HN46-0AA0, 25 A rated continuous current, 4-pole, ETU350 electronic trip unit, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2025-8HN46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2025-8HN46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C25 A
Current at 60 °C25 A
Current at 65 °C25 A
Current at 70 °C25 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V52.5 kA
Power loss, max.0.5 W
3VA2025-8HN46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2025-8HN46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2025-8HN46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2025-8HN46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2025-8HN46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2025-8HN46-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for 25 A continuous current at 40 °C through 70 °C ambient — no derating needed across that span. Breaking capacity is 440 kA at 240 V, 330 kA at 415 V and 440 V, 220 kA at 500 V, and 52.5 kA at 690 V — figures that put it in the high-interrupting category for industrial mains distribution.

The 4-pole footprint matches standard MCCB mounting in SENTRON distribution boards and third-party enclosures.

Frequently asked questions

What are the key ratings for 3VA2025-8HN46-0AA0?

Continuous current is 25 A across the full -25 °C to 70 °C operating range. Breaking capacity reaches 440 kA at 240 V and 330 kA at 415 V. The trip unit is an ETU350 electronic type. Rated insulation voltage is 800 V.

How do I get pricing and availability for this MCCB?

Submit an RFQ through this listing. The part is sourced through independent distribution; current pricing and stock position are confirmed at quote time.

Will 3VA2025-8HN46-0AA0 drop into a panel specified for 3VA2025-8HN42-0AA0?

Both share the same 4-pole SENTRON 3VA frame dimensions (86 mm deep, 140 mm wide, 181 mm high), so the physical footprint is identical. The difference is the trip unit — the -46 suffix carries the ETU350 electronic trip, while the -42 suffix uses a different trip variant. Panel cutouts and bus connections are the same; verify the trip coordination study before swapping.

MPN
3VA2025-8HN46-0AA0