SENTRON 3VA2040-5JQ42-0AA0 — 40 A MCCB with ground-fault monitoring
Breaking capacity across voltage tiers
This breaker delivers 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V.
Ground-fault and communication
Built-in ground-fault monitoring uses summation current formation on L+N conductors — catches leakage without an external GFCI module. Communication function is onboard, so it can talk to a BMS or energy management system over the SENTRON bus. No undervoltage release or trip indicator on this variant; those are separate order-code options.
Listed as current-production — no end-of-life notice on this variant.