Skip to main content
Siemens 3VA2040-6HL32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2040-6HL32-0AA0 SENTRON MCCB, 40 A, 3-Pole, ETU32

MPN3VA2040-6HL32-0AA0
Active

Siemens SENTRON 3VA2040-6HL32-0AA0, molded case circuit breaker, 3-pole, 40 A continuous, ETU320 electronic trip unit, 242 kA at 240 V, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2040-6HL32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON

Ratings

3VA2040-6HL32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C40 A
Current at 60 °C40 A
Current at 65 °C40 A
Current at 70 °C40 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3 kA
Power loss, max.2.2 W

Protection & Trip Unit

3VA2040-6HL32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2040-6HL32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2040-6HL32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2040-6HL32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2040-6HL32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB is and what the ratings mean for your panel

The Siemens SENTRON 3VA2040-6HL32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 40 A continuous current, designed for line protection in distribution panels. The ETU320 electronic trip unit gives you adjustable overload and short-circuit protection curves, so you can coordinate selectivity downstream without swapping trip units. The 242 kA interrupting rating at 240 V means this breaker can safely clear a fault up to that level — critical for high-fault-capacity service entrances or transformer secondaries where available fault current is high. At 415 V and 440 V it still holds 187 kA, and at 500 V it's rated 121 kA; only at 690 V does it drop to 3 kA, so keep that in mind if you're on a 690 V system. The 800 V rated insulation voltage confirms it's built for 480/600 V class panels with margin. The continuous current rating holds flat at 40 A from 40 °C all the way up to 70 °C ambient — no derating needed in a warm enclosure. That's unusual for an MCCB and simplifies panel thermal calculations. The IP40 front protection means it's fine in a clean indoor panel but not for washdown environments. Mounting dimensions are 105 mm wide, 181 mm high, 86 mm deep — standard 3-pole MCCB footprint for DIN-rail or screw-mount panel integration.

How it compares to the 3VA1110-5ED32-0AA0 sibling

The closest functional peer in the SENTRON 3VA family is the 3VA1110-5ED32-0AA0. Both are 3-pole MCCBs with electronic trip units, but the 3VA1110 series is a physically smaller frame (typically 76 mm wide vs. 105 mm) with lower interrupting ratings — it won't match the 242 kA at 240 V that this 3VA2040 frame delivers. If your panel was specified around the 3VA1110-5ED32-0AA0, the 3VA2040-6HL32-0AA0 will not drop in without rewiring: the wider footprint and different mounting hole pattern mean a new drill template. Use the 3VA2040 when you need the higher fault-interrupt capacity or the flat 40 A thermal curve; stay with the 3VA1110 if panel space is tight and fault current is lower.

Frequently asked questions

How do I get current pricing and availability for 3VA2040-6HL32-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is 3VA2040-6HL32-0AA0's interrupting rating at 240 V?

The interrupting rating is 242 kA at 240 V. At 415 V and 440 V it's 187 kA, at 500 V it's 121 kA, and at 690 V it's 3 kA.

What trip unit does 3VA2040-6HL32-0AA0 use?

It uses the ETU320 electronic trip unit, providing adjustable overload and short-circuit protection curves for selectivity coordination.

MPN
3VA2040-6HL32-0AA0