Breaking capacity — where it interrupts
This MCCB delivers 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 3 kA at 690 V. The steep drop to 3 kA at 690 V means this is really a 480 V / 600 V class breaker; don't spec it for 690 V applications unless the fault current is well under 3 kA.
Mounting and environment
Dimensions are 105 mm wide, 181 mm tall, 86 mm deep — standard SENTRON 3VA2 footprint for a 3-pole frame. Bolts into a panel or mounts on a mounting plate; no DIN rail on this frame size.