The 800 V rated insulation voltage and the breaking capacity profile — 330 kA at 240 V, 242 kA at 415/440 V, 187 kA at 500 V, and 3 kA at 690 V — tell you this breaker is built for high-fault-capacity main or feeder duty, not branch-circuit light loads.
Sizing and thermal behaviour
Maximum power loss is 1.2 W, negligible for heat budgeting. The adjustable trip range spans 60 A minimum to 480 A maximum, so the ETU850 can be set to coordinate with downstream breakers or protect a specific load profile. The 3-pole construction suits three-phase systems; the lack of an undervoltage release or voltage trip means external monitoring or shunt-trip accessories would need to be added if those functions are required.