Skip to main content
Siemens 3VA2063-5HL32-0DE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2063-5HL32-0DE0 SENTRON MCCB, 63 A, 187 kA at 240

MPN3VA2063-5HL32-0DE0

Siemens SENTRON 3VA2063-5HL32-0DE0, molded case circuit breaker, 3-pole, 63 A rated continuous current Iu, 187 kA interrupting at 240 V, line protection version with undervoltage release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2063-5HL32-0DE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2063-5HL32-0DE0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V76 kA
Breaking capacity at 690 V3 kA
Power loss, max.5.4 W
3VA2063-5HL32-0DE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
3VA2063-5HL32-0DE0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2063-5HL32-0DE0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA2063-5HL32-0DE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2063-5HL32-0DE0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.1 in
Width (in)4.1 in
Depth (in)3.4 in

Product details

The Siemens SENTRON 3VA2063-5HL32-0DE0 is a 3-pole molded case circuit breaker (MCCB) rated for 63 A continuous current (Iu) and built for line protection duty — meaning it sits upstream protecting a feeder or a large load, not a motor branch circuit with its own overload relay. The interrupting ratings tell you where it can go: 187 kA at 240 V, 121 kA at 415 V and at 440 V, 76 kA at 500 V, and 3 kA at 690 V. The 63 A rating holds flat across the full ambient range from 40 °C to 70 °C, so no derating headache in a warm enclosure.

Built-in undervoltage release and aux switching

It also carries four auxiliary switches in the HQ configuration (high-auxiliary switching capacity), so you get status feedback for each pole without adding external contact blocks. The auxiliary release order code is 3VA9608-0BB25 if you need a spare or a replacement module. No communication function on this variant — it's a straight electromechanical breaker, no bus coupler inside.

Panel fit and physical integration

Dimensions are 105 mm wide, 181 mm tall, 86 mm deep — a standard SENTRON 3VA2 frame footprint. Rated insulation voltage Ui is 800 V, so it's comfortable on 480/277 V and 600 V systems. Storage range is -40 °C to 80 °C; operating range is -25 °C to 70 °C.

Frequently asked questions

What is the interrupting rating of 3VA2063-5HL32-0DE0 at 240 V?

187 kA at 240 V, which is the highest interrupting rating for this breaker and suits high-fault-current distribution points.

Does 3VA2063-5HL32-0DE0 include an undervoltage release?

Yes, it ships with a factory-fitted undervoltage release (UVR) as the design of auxiliary release.

Where can I buy 3VA2063-5HL32-0DE0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

MPN
3VA2063-5HL32-0DE0