Siemens 3VA2063-5HL32-0DL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2063-5HL32-0DL0 SENTRON MCCB, 63 A, 3-Pole, 187 k

MPN3VA2063-5HL32-0DL0

Siemens SENTRON 3VA2063-5HL32-0DL0, molded case circuit breaker, 3-pole, 63 A continuous, 187 kA at 240 V, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2063-5HL32-0DL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20635HL320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2063-5HL32-0DL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.7.9 W
3VA2063-5HL32-0DL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2063-5HL32-0DL0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2063-5HL32-0DL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA2063-5HL32-0DL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2063-5HL32-0DL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Integrator’s terse spec recap

The Siemens SENTRON 3VA2063-5HL32-0DL0 is a 3-pole molded case circuit breaker (MCCB) rated for 63 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Breaking capacity hits 187 kA at 240 V, 121 kA at 415/440 V, 75.6 kA at 500 V, and 3 kA at 690 V, so it handles high-fault utility feeds in North American and IEC 50 kA-class installations without cascading upstream.

Line protection build and auxiliary complement

That gives the panel builder remote status and trip indication without adding external relays. Dimensions are 105 mm wide, 181 mm high, 86 mm deep — standard SENTRON 3VA frame size for 63 A.

Frequently asked questions

What is the breaking capacity of 3VA2063-5HL32-0DL0 at different voltages?

187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V. The 187 kA at 240 V covers high-fault utility feeds common in North American panels.

What auxiliary switches come with this MCCB?

It includes 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch HQ, plus an undervoltage release (UVR). That covers remote status and trip indication without extra hardware.

Where can I buy 3VA2063-5HL32-0DL0?

This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

MPN
3VA2063-5HL32-0DL0