Skip to main content
Siemens 3VA2063-5HL32-0KH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2063-5HL32-0KH0 SENTRON MCCB, 63 A, 187 kA at 240

MPN3VA2063-5HL32-0KH0

Siemens SENTRON 3VA2063-5HL32-0KH0, molded case circuit breaker, 3-pole, 63 A, breaking capacity 187 kA at 240 V, ETU320 electronic trip unit, shunt trip, 2 aux + 1 alarm switch.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2063-5HL32-0KH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2063-5HL32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2063-5HL32-0KH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.6375 A
Current at 60 °C58.275 A
Current at 65 °C55.9125 A
Current at 70 °C53.55 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V3.4 kA
Power loss, max.5.4 W

Protection & Trip Unit

3VA2063-5HL32-0KH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320

Construction & Connection

3VA2063-5HL32-0KH0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2063-5HL32-0KH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2063-5HL32-0KH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2063-5HL32-0KH0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

Integrator's note — 3VA2063-5HL32-0KH0

The Siemens 3VA2063-5HL32-0KH0 is a SENTRON molded case circuit breaker, 3-pole, rated 63 A continuous current at 40 °C. Its headline breaking capacity reaches 187 kA at 240 V and 121 kA at 415 V — that is the fault-clearing ceiling for high-available-fault-current panels, typical at a utility transformer secondary or a large motor control center. The ETU320 electronic trip unit provides adjustable overload and short-circuit protection curves, with a shunt trip (STL) for remote opening and an integrated auxiliary trip module (3VA9688-0BL33).

Breaking capacity and selectivity

At 240 V the 187 kA rating means this MCCB can safely interrupt faults up to that level without cascading upstream — critical for selective coordination in a distribution board. At 690 V the rating drops to 3.4 kA, so for 690 V applications the breaker is limited to lower-fault branches. The 63 A continuous rating holds flat through 50 °C; above that it derates to 53.55 A at 70 °C, so panel ambient temperature must be factored into the load schedule.

Panel integration and wiring

The 3VA2063-5HL32-0KH0 mounts on a DIN rail or panel-mount adapter. Dimensions: 105 mm wide, 181 mm high, 86 mm deep — fits a standard MCCB slot in a SENTRON distribution board or a third-party enclosure with the appropriate cutout. The shunt trip (STL) requires a separate control voltage; no undervoltage release is fitted. Auxiliary contacts include 2 form-C aux switches plus 1 trip alarm switch (HQ version).

Frequently asked questions

Where can I buy 3VA2063-5HL32-0KH0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the closest functional second-source for 3VA2063-5HL32-0KH0?

The 3VA1110-5EE32-0JA0 is a smaller-frame SENTRON MCCB (100 A frame, lower breaking capacity) — it will not drop into a panel wired for the 3VA2063 without rewiring the bus bars and adjusting the cutout. The 3VA2063 is the correct form-factor for 63 A line protection with high interrupting capacity.

What is 3VA2063-5HL32-0KH0's listed depth?

86 mm.

What is 3VA2063-5HL32-0KH0's listed width?

105 mm.

Will 3VA2063-5HL32-0KH0 drop into a panel specified around 3VA1110-5EE32-0JA0 without rewiring?

No — the 3VA2063 is a larger-frame MCCB (105 mm wide vs the 3VA1110's narrower footprint) and has a different bus-bar pitch. Panel cutout and bus connections must be reworked.

What compliance documentation does Siemens provide for 3VA2063-5HL32-0KH0?

The SENTRON series carries UL, CSA, and IEC certifications; RoHS and REACH declarations are available from Siemens documentation. Specific cert numbers are not listed in this record.

MPN
3VA2063-5HL32-0KH0