Skip to main content
Siemens 3VA2063-5HL32-0KL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2063-5HL32-0KL0 SENTRON MCCB, 63 A, 3-Pole, 187 k

MPN3VA2063-5HL32-0KL0

Siemens SENTRON 3VA2063-5HL32-0KL0, molded case circuit breaker, 3-pole, 63 A continuous, 187 kA breaking at 240 V, line protection, with shunt trip and auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2063-5HL32-0KL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20635HL320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22

Ratings

3VA2063-5HL32-0KL0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.5.4 W

Protection & Trip Unit

3VA2063-5HL32-0KL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2063-5HL32-0KL0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2063-5HL32-0KL0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4

Environmental

3VA2063-5HL32-0KL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2063-5HL32-0KL0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB is and what it does

The Siemens 3VA2063-5HL32-0KL0 is a SENTRON molded case circuit breaker (MCCB) rated for 63 A continuous current on a 3-pole line-protection design. It breaks up to 187 kA at 240 V and 121 kA at 415 V, so it handles high-fault-current panels without cascading upstream — typical for main or feeder duty in industrial switchboards.

Breaking capacity and what it means for your panel

At 240 V the interrupting rating is 187 kA; at 415 V it is 121 kA, and at 500 V it drops to 75.6 kA. At 690 V the rating is 3 kA — this breaker is sized for low-voltage distribution up to 500 V, not 690 V main duty. The 63 A rating holds flat from 40 °C through 70 °C, so no derating needed in a warm enclosure.

Built-in auxiliaries and release options

This variant ships with two auxiliary switches, one trip alarm switch, one electrical alarm switch, and a shunt trip (STL) release. The shunt trip lets you remotely trip the breaker from a PLC or emergency-stop circuit without an undervoltage release. No ground-fault monitoring module is included.

Physical fit and panel integration

Dimensions are 105 mm wide, 181 mm tall, 86 mm deep — standard 3-pole MCCB footprint for a 63 A frame. Mounts on a DIN rail or directly to a backplate. The trip indicator and voltage trigger are visible through the front cover, handy for quick fault isolation during commissioning.

Frequently asked questions

Where can I buy 3VA2063-5HL32-0KL0 and how do I get a price?

Sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What are the key ratings of 3VA2063-5HL32-0KL0?

Continuous current 63 A, 3-pole, breaking capacity 187 kA at 240 V and 121 kA at 415 V, with shunt trip and auxiliary switches.

Will 3VA2063-5HL32-0KL0 drop into a panel specified around 3VA1110-5EF32-0AM0?

The 3VA2063 frame is physically larger — 105 mm wide vs the 3VA1110's 70 mm width — so it will not fit the same DIN-rail footprint or panel cutout without rewiring and re-drilling.

MPN