Siemens 3VA2063-5HL36-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2063-5HL36-0HC0 SENTRON MCCB, 63 A, 3-Pole, 187 k

MPN3VA2063-5HL36-0HC0

Siemens SENTRON 3VA2063-5HL36-0HC0, molded case circuit breaker, 3-pole, 63 A, 187 kA at 240 V, line protection, with shunt trip and 2 auxiliary switches HQ.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2063-5HL36-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20635HL360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2063-5HL36-0HC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.5.4 W

Protection & Trip Unit

3VA2063-5HL36-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2063-5HL36-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2063-5HL36-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2063-5HL36-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2063-5HL36-0HC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

63 A MCCB with shunt trip — line protection for distribution panels

The Siemens SENTRON 3VA2063-5HL36-0HC0 is a 3-pole molded case circuit breaker rated for 63 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Breaking capacity reaches 187 kA at 240 V, 121 kA at 415/440 V, 75.6 kA at 500 V, and 3 kA at 690 V, so it handles high-fault utility feeds and transformer secondaries without cascading upstream. The built-in shunt trip (STL) and two HQ auxiliary switches give remote trip and status feedback for automated or safety-monitored circuits.

Fit and panel integration

At 105 mm wide × 181 mm tall × 86 mm deep, this MCCB fits standard SENTRON mounting footprints and leaves room for adjacent breakers and accessories on the DIN rail or panel-mount plate. The 63 A frame keeps power loss at 5.4 W maximum, so thermal rise inside a sealed enclosure stays manageable without forced ventilation.

Frequently asked questions

Where can I buy 3VA2063-5HL36-0HC0 and how do I get a price?

Sourced to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What breaking capacity does this MCCB have at 240 V and 415 V?

187 kA at 240 V and 121 kA at 415 V, covering high-fault commercial and industrial service entrances.

What auxiliary and release options are fitted on 3VA2063-5HL36-0HC0?

It includes a shunt trip (STL) for remote tripping and two HQ auxiliary switches for status feedback.

MPN