Siemens 3VA2063-5HL36-0JH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2063-5HL36-0JH0 SENTRON MCCB, 63 A, 3-Pole, 187 k

MPN3VA2063-5HL36-0JH0

Siemens SENTRON 3VA2063-5HL36-0JH0, molded case circuit breaker, 3-pole, 63 A rated continuous current, 187 kA interrupting at 240 VAC, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2063-5HL36-0JH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20635HL360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2063-5HL36-0JH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.5.4 W

Protection & Trip Unit

3VA2063-5HL36-0JH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2063-5HL36-0JH0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2063-5HL36-0JH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2063-5HL36-0JH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2063-5HL36-0JH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2063-5HL36-0JH0 is a 3-pole molded case circuit breaker (MCCB) rated for 63 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. It's designed for line protection in distribution panels where you need a fixed thermal-magnetic trip and a healthy interrupting rating: 187 kA at 240 VAC, 121 kA at 415/440 VAC, 75.6 kA at 500 VAC, and 3 kA at 690 VAC. That 187 kA figure at 240 V means it can handle high-fault scenarios common on the secondary side of large step-down transformers without cascading upstream.

Panel fit and integration

The 3VA2063-5HL36-0JH0 measures 105 mm wide, 181 mm tall, and 86 mm deep. That 105 mm width on a 3-pole frame means it fits standard Siemens SENTRON mounting bases and busbar systems — no custom drilling. It ships with a shunt trip (STL) auxiliary release and a built-in trip indicator plus voltage trigger, plus 2 auxiliary switches and 1 trip alarm switch (HQ type). That switch complement is enough to signal the breaker state back to a PLC or annunciator without adding an external relay bank. Operating range is -25 °C to 70 °C ambient; storage from -40 °C to 80 °C.

Maximum power dissipation is 5.4 W at rated load — negligible for thermal budgeting in a crowded enclosure, but worth noting if you're packing a dozen breakers in a sealed box. The continuous current rating holds at 63 A from 40 °C through 70 °C ambient; that's a flat derating curve, meaning you don't have to recalculate for a warm panel. Minimum trip setting is 95 A, maximum 756 A on the magnetic instant trip — wide adjustment range for coordinating with downstream breakers.

Frequently asked questions

Where can I buy 3VA2063-5HL36-0JH0 and get current pricing?

This part is sourced and quoted to order through our industrial automation distribution channel. Submit an RFQ for current pricing and availability — confirmed at quote time.

What are the key interrupting ratings for 3VA2063-5HL36-0JH0?

187 kA at 240 VAC, 121 kA at 415 VAC and 440 VAC, 75.6 kA at 500 VAC, and 3 kA at 690 VAC. The 187 kA at 240 V is the standout figure — it handles high-fault secondary-side transformer faults without cascading.

What is the continuous current rating and does it derate with temperature?

Rated 63 A continuous from 40 °C through 70 °C ambient — no derating needed across that range. That's a flat thermal curve, unusual for breakers that typically step down above 40 °C.

What auxiliary switches and releases come with this breaker?

It includes 2 auxiliary switches plus 1 trip alarm switch (HQ type), and a shunt trip (STL) auxiliary release. That's enough to signal open/trip status back to a PLC without extra hardware.

MPN