Skip to main content
Siemens 3VA2063-5HL36-0KA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2063-5HL36-0KA0 SENTRON MCCB, 63 A, 3-Pole, 187 k

MPN3VA2063-5HL36-0KA0

Siemens SENTRON 3VA2063-5HL36-0KA0, molded case circuit breaker, 3-pole, 63 A, line protection with shunt trip release, breaking capacity 187 kA at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2063-5HL36-0KA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20635HL360AA0

Ratings

3VA2063-5HL36-0KA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.5.4 W

Protection & Trip Unit

3VA2063-5HL36-0KA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2063-5HL36-0KA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2063-5HL36-0KA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2063-5HL36-0KA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2063-5HL36-0KA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

63 A MCCB with shunt trip — what the ratings mean for your panel

The Siemens SENTRON 3VA2063-5HL36-0KA0 is a 3-pole molded case circuit breaker rated for 63 A continuous current with no derating across the full 40 °C to 70 °C operating range — meaning you can load it to 63 A in a warm enclosure without bumping the frame size. The 187 kA breaking capacity at 240 V drops to 121 kA at 415 V and 440 V, then to 75.6 kA at 500 V, and finally to 3 kA at 690 V. That steep falloff at 690 V means this breaker is sized for 400 V-class distribution panels, not 690 V motor circuits. The built-in shunt trip (STL) release lets a remote signal or safety relay trip the breaker independently of overcurrent — useful for emergency-off or interlock circuits where you need to kill power without pulling the handle.

Panel fit and footprint

At 105 mm wide × 181 mm tall × 86 mm deep, this MCCB fits standard SENTRON 3VA panel cutouts and busbar systems. The 86 mm depth (3.39 in) is shallow enough for 200 mm-deep enclosures with room for wiring gutters. No undervoltage release or ground-fault module on this variant — the only auxiliary is the shunt trip, so verify your trip-coil wiring before commissioning.

Frequently asked questions

Where can I buy 3VA2063-5HL36-0KA0 and what is the lead time?

This MCCB is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — lead time is confirmed at quote time.

What is the breaking capacity of 3VA2063-5HL36-0KA0 at different voltages?

187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V. The steep drop at 690 V means this breaker is designed for 400 V-class distribution, not 690 V motor circuits.

Does 3VA2063-5HL36-0KA0 derate at high ambient temperatures?

No — it holds the full 63 A continuous rating from 40 °C through 70 °C ambient. No derating curve to calculate for warm enclosures.

What auxiliary release does this MCCB include?

It has a shunt trip (STL) release for remote tripping. No undervoltage release or ground-fault monitoring is fitted on this variant.

MPN
3VA2063-5HL36-0KA0