Skip to main content
Siemens 3VA2063-5HM46-0AL0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2063-5HM46-0AL0 SENTRON MCCB, 63 A, 187 kA at 240

MPN3VA2063-5HM46-0AL0

Siemens SENTRON 3VA2063-5HM46-0AL0, molded case circuit breaker, 4-pole, 63 A, ETU330 electronic release, line protection, 187 kA at 240 V, 121 kA at 415 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2063-5HM46-0AL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2063-5HM46-0AL0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V76 kA
Breaking capacity at 690 V3 kA
Power loss, max.5.4 W
3VA2063-5HM46-0AL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU330
3VA2063-5HM46-0AL0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2063-5HM46-0AL0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
3VA2063-5HM46-0AL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2063-5HM46-0AL0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.1 in
Width (in)5.5 in

Product details

What this 63 A SENTRON MCCB does in a panel

The Siemens 3VA2063-5HM46-0AL0 is a 4-pole molded case circuit breaker from the SENTRON family, rated 63 A continuous current at 40 °C through 70 °C — no derating needed across that span, which simplifies panel thermal budgeting. It carries an ETU330 electronic trip unit with adjustable long-time delay (tr min 0.5 s, tr max 17 s) and adjustable N-conductor protection (OFF or 100%). The interrupting ratings are the headline: 187 kA at 240 V, 121 kA at 415 V and at 440 V, 76 kA at 500 V, and 3 kA at 690 V.

Ground fault monitoring is built in via summation current formation of L + N conductors, which saves adding an external GF relay for grounded-neutral systems.

Trip unit and protection settings

The ETU330 electronic release provides adjustable long-time pickup and delay, plus fixed short-time and instantaneous settings typical of a line-protection MCCB. The N-conductor protection can be set to OFF or 100% of the phase rating, which is useful for panels feeding mixed single-phase and three-phase loads where the neutral may carry near-phase current. Power loss is 5.4 W maximum — negligible for thermal coordination in a crowded enclosure.

Frequently asked questions

Where can I buy 3VA2063-5HM46-0AL0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What are the interrupting ratings of this MCCB?

187 kA at 240 V, 121 kA at 415 V and at 440 V, 76 kA at 500 V, and 3 kA at 690 V.

What is the depth of 3VA2063-5HM46-0AL0?

The depth is 86 mm.

Does this breaker have ground fault protection?

Yes, it includes ground fault monitoring via summation current formation of the L + N conductors.

MPN
3VA2063-5HM46-0AL0