Skip to main content
Siemens 3VA2063-5HN32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2063-5HN32-0AC0 SENTRON MCCB, 63 A, 3-Pole, 187 k

MPN3VA2063-5HN32-0AC0

Siemens SENTRON 3VA2063-5HN32-0AC0, 3-pole molded case circuit breaker, 63 A continuous rating, 187 kA interrupting capacity at 240 V AC, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2063-5HN32-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20635HN320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA2063-5HN32-0AC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.5.4 W

Protection & Trip Unit

3VA2063-5HN32-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2063-5HN32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2063-5HN32-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA2063-5HN32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2063-5HN32-0AC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Siemens 3VA2063-5HN32-0AC0 — 63 A SENTRON MCCB, 187 kA SCCR

The Siemens 3VA2063-5HN32-0AC0 is a SENTRON 3-pole molded case circuit breaker rated for 63 A continuous current at 40 °C through 70 °C with no derating across that band — the full 63 A holds all the way to 70 °C ambient. Its interrupting capacity hits 187 kA at 240 V AC, 121 kA at 415/440 V, and 75.6 kA at 500 V; at 690 V it still clears 3 kA. That 187 kA figure at 240 V means it can be placed upstream of a high-fault panel without needing a current-limiting fuse ahead of it — the breaker itself handles the full available fault current at that voltage level. Rated insulation voltage is 800 V, and the unit is designed for line protection — not motor protection or ground-fault monitoring. It ships with the basic switch 3VA20635HN320AA0 and carries two HQ auxiliary switches. No undervoltage release, no voltage trip, no communication function. This is a straightforward, high-interrupting MCCB for distribution panels where selectivity and fault-clearing headroom are the priorities.

Panel Fit & Mounting

Dimensions: 105 mm wide, 181 mm tall, 86 mm deep. The 105 mm width is the standard 4-module footprint for SENTRON 3VA breakers — it drops into the same DIN-rail or panel-mount cutout as other 3VA 3-pole units. Operating temperature range is -25 °C to 70 °C; storage from -40 °C to 80 °C. Maximum power loss is 5.4 W.

Compliance & Approvals

As a SENTRON MCCB, the 3VA2063-5HN32-0AC0 carries the standard Siemens compliance documentation for the series — RoHS, REACH, UL, and IEC certifications are part of the product's regulatory package. Specific certificate numbers and declaration files are available with the datasheet set.

Frequently asked questions

What is the interrupting capacity of 3VA2063-5HN32-0AC0 at 240 V?

187 kA at 240 V AC, which allows upstream placement without a current-limiting fuse at that voltage level.

How do I get pricing and availability for 3VA2063-5HN32-0AC0?

The part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

Will 3VA2063-5HN32-0AC0 replace 5SQ2370-2YA05 in an existing panel?

The 3VA2063-5HN32-0AC0 is a different series from the 5SQ2370 family. While both are 3-pole MCCBs, verify the physical footprint and terminal arrangement against your panel cutout and bus connection before substitution — the 105 mm width is standard for 3VA but may differ from the 5SQ2370 mounting pattern.

MPN
3VA2063-5HN32-0AC0