Specifications

Identification

3VA2063-5HN32-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20635HN320AA0

Ratings

3VA2063-5HN32-0HA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.5.4 W

Protection & Trip Unit

3VA2063-5HN32-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2063-5HN32-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2063-5HN32-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2063-5HN32-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2063-5HN32-0HA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Siemens 3VA2063-5HN32-0HA0 — 63 A MCCB for Line Protection

The Siemens 3VA2063-5HN32-0HA0 is a SENTRON molded case circuit breaker (MCCB) rated for 63 A continuous current, 3-pole, designed for line protection in distribution panels. Its 187 kA breaking capacity at 240 V and 121 kA at 415 V means it can safely interrupt very high fault currents without upstream cascading — critical for high-available-fault-current installations like substations or large motor control centers. The 63 A rating holds flat from 40 °C to 70 °C, so no derating is needed across typical panel ambient temperatures.

Breaking Capacity and Selectivity

The interrupting ratings drop with system voltage: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V. For a 480 V panel (common in North America), the 75.6 kA SCCR gives headroom for most industrial service entrances. The 800 V rated insulation voltage supports use in 690 V systems where the available fault current is low. The shunt trip release (STL) allows remote tripping via a control signal — useful for emergency-stop circuits or supervisory shutdown.

Frequently asked questions

Where can I buy 3VA2063-5HN32-0HA0 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote — availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA2063-5HN32-0HA0 at 415 V?

The breaking capacity at 415 V is 121 kA.

What compliance documentation is available for this MCCB?

The evidence does not list specific compliance marks (UL, CE, RoHS) for this order code. Typical SENTRON MCCBs carry IEC/EN 60947-2 certification; verify the specific documentation with the supplier at quote time.