Siemens 3VA2063-5HN36-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2063-5HN36-0AD0 SENTRON MCCB, 63 A, 3-Pole, 187 k

MPN3VA2063-5HN36-0AD0

Siemens SENTRON 3VA2063-5HN36-0AD0, molded case circuit breaker, 3-pole, 63 A continuous, line protection, 187 kA at 240 V, 121 kA at 415 V, 3 auxiliary switches HQ.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2063-5HN36-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20635HN360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA2063-5HN36-0AD0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.5.4 W
3VA2063-5HN36-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2063-5HN36-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2063-5HN36-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA2063-5HN36-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2063-5HN36-0AD0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The Siemens SENTRON 3VA2063-5HN36-0AD0 is a 3-pole molded case circuit breaker rated for 63 A continuous current, designed for line protection in industrial distribution panels. Its 187 kA interrupting capacity at 240 V and 121 kA at 415 V give it the headroom to clear high-fault conditions without cascading upstream — a key consideration when coordinating selective tripping on a main or feeder breaker.

Breaking capacity and thermal performance

This MCCB delivers 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V. That voltage-dependent curve is typical of a current-limiting design — the arc extinction method changes effectiveness above 500 V, so the 690 V rating drops sharply. For a 480 V panel (common in North American industrial plants), the 75.6 kA figure is the one to size against the available fault current. The continuous current rating holds at 63 A across the entire ambient temperature range from 40 °C to 70 °C — no derating needed. That simplifies panel layout if the breaker sits near other heat sources inside a sealed enclosure. Power loss is 5.4 W maximum.

At 105 mm wide, 181 mm tall, and 86 mm deep, this breaker fits the standard SENTRON 3VA mounting footprint.

Auxiliary switching and options

This variant ships with three auxiliary switches (HQ type) integrated. The base switch assembly part number is 3VA20635HN360AA0.

Frequently asked questions

Where can I buy 3VA2063-5HN36-0AD0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What is the breaking capacity of this MCCB at 480 V?

At 500 V the interrupting rating is 75.6 kA, which is the figure to use for 480 V panel sizing. At 240 V it is 187 kA, at 415 V it is 121 kA, and at 690 V it drops to 3 kA.

Does this breaker require derating at high ambient temperatures?

No. The 63 A continuous rating holds from 40 °C through 70 °C ambient with no derating required.

What is the depth of 3VA2063-5HN36-0AD0?

The depth is 86 mm (3.39 in). This is the dimension to check against enclosure gland-plate clearance in retrofit panels.