The Siemens SENTRON 3VA2063-5HN36-0BL0 is a 3-pole molded case circuit breaker (MCCB) rated for 63 A continuous current across its full ambient temperature range from 40 °C to 70 °C — no derating needed up to the 70 °C operating maximum. Breaking capacity reaches 187 kA at 240 V AC, stepping down to 121 kA at 415/440 V, 75.6 kA at 500 V, and 3 kA at 690 V. This is a line-protection design (not motor-protection), so the thermal-magnetic trip curve is shaped for feeder and distribution duty rather than motor inrush.
The auxiliary switch stack gives the PLC or BMS a positive status feedback on breaker position (open/closed) and trip condition, without needing a separate contactor block.
The trip indicator is present for visual fault identification without opening the panel.