Skip to main content
Siemens 3VA2063-5HN36-0KA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2063-5HN36-0KA0 SENTRON MCCB, 63 A, 3-Pole, ETU35

MPN3VA2063-5HN36-0KA0

Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2063-5HN36-0KA0, 63 A, 3-pole, ETU350 electronic trip unit, line protection, shunt trip (STL), 187 kA at 240 V, 86 x 105 x 181 mm.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2063-5HN36-0KA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2063-5HN36-0AA0
3VA2063-5HN36-0KA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.6375 A
Current at 60 °C58.275 A
Current at 65 °C55.9125 A
Current at 70 °C53.55 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V3.4 kA
Power loss, max.5.4 W
3VA2063-5HN36-0KA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2063-5HN36-0KA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2063-5HN36-0KA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2063-5HN36-0KA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2063-5HN36-0KA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

What this 3VA2063-5HN36-0KA0 brings to a panel

Breaking capacity hits 187 kA at 240 V AC and holds 121 kA at 415/440 V, then drops to 79 kA at 500 V and 3.4 kA at 690 V. The ETU350 release gives you adjustable long-time, short-time, and instantaneous pickup, plus ground-fault capability if you add the optional module.

Rated 63 A from 40 °C through 50 °C; above that it derates linearly to 53.55 A at 70 °C. The 5.4 W max power loss is modest; no special ventilation required in a typical IP54 enclosure.

Frequently asked questions

What is 3VA2063-5HN36-0KA0's listed depth (86 mm) on this component line?

The depth is 86 mm, width 105 mm, height 181 mm — standard 3VA2 footprint for DIN-rail or panel-mount installation.

MPN
3VA2063-5HN36-0KA0