Skip to main content
Siemens 3VA2063-5HN42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2063-5HN42-0AA0 SENTRON MCCB, 63 A, 4-Pole, ETU35

MPN3VA2063-5HN42-0AA0
Active

Siemens SENTRON molded case circuit breaker, 3VA2063-5HN42-0AA0, 63 A, 4-pole, ETU350 electronic trip unit, 187 kA interrupting at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA2063-5HN42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2063-5HN42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.5.4 W
3VA2063-5HN42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2063-5HN42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2063-5HN42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2063-5HN42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2063-5HN42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.13 in
Width (in)5.51 in
Depth (in)3.39 in

Product details

This is a line-protection design — meaning it's configured for feeder and distribution duty, not motor-starting or generator protection. The ETU350 provides adjustable long-time, short-time, instantaneous, and ground-fault protection curves, which gives the specifying engineer selectivity headroom downstream without sacrificing trip speed on a hard fault.

Interrupting capacity and voltage class

This MCCB delivers 187 kA interrupting capacity at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V.

That's unusual for a molded case breaker; most lose 10–15 % by 60 °C. Power dissipation at full load is 5.4 W, which is manageable for dense panel layouts.

Dimensions are 181 mm height, 140 mm width, 86 mm depth. The 140 mm width for a 4-pole frame is standard for this SENTRON class; it matches the mounting footprint of the 3VA2 family, so a panel drilled for a 3VA2040-8HN42-0AA0 will accept this unit without re-drilling or bus-bar rework, provided the lugs accept the same conductor size.

The lifecycle stage is listed as current — meaning Siemens has not issued an end-of-life notice, and the part remains in the active catalog. No successor order code has been published.

Front-face protection class is IP40 — suitable for dry indoor panel mounting where no water jets or dust ingress are expected. The breaker carries no undervoltage release, no shunt trip, and no communication function as configured; it is a standalone thermal-magnetic replacement with electronic trip adjustment accessible on the front face.

Frequently asked questions

Where can I buy 3VA2063-5HN42-0AA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock figures or lead-time numbers are published here.

Will 3VA2063-5HN42-0AA0 fit in a panel drilled for 3VA2040-8HN42-0AA0?

Yes, the 140 mm width and 181 mm height match the 3VA2 family mounting footprint. The 86 mm depth is the same behind-panel dimension. No bus-bar rework or re-drilling should be required, provided the line and load lugs accept the same conductor cross-section.

What is the interrupting capacity of this MCCB at 240 V?

187 kA at 240 V. That is the highest interrupting rating on this breaker's voltage table — it can clear a fault on a low-voltage transformer secondary without upstream coordination issues.

Does the 63 A rating need derating at high ambient temperatures?

No. The 63 A continuous rating holds flat from 40 °C to 70 °C ambient — no derating required within that range.

MPN
3VA2063-5HN42-0AA0