Skip to main content
Siemens 3VA2063-5JP32-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2063-5JP32-0AF0 SENTRON MCCB, 63 A, 187 kA at 240

MPN3VA2063-5JP32-0AF0

Siemens SENTRON 3VA2063-5JP32-0AF0, molded case circuit breaker, 3-pole, 63 A, 187 kA at 240 V, ETU550 electronic release, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2063-5JP32-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA2063-5JP32-0AF0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V76 kA
Breaking capacity at 690 V3 kA
Power loss, max.5.4 W

Protection & Trip Unit

3VA2063-5JP32-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550

Construction & Connection

3VA2063-5JP32-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2063-5JP32-0AF0 — Accessories & Functions
ParameterValue
Communication functionYes
Measurement functionNo
Motor drive optionYes

Environmental

3VA2063-5JP32-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2063-5JP32-0AF0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.1 in
Width (in)4.1 in

Product details

What the ratings mean for your panel

The Siemens 3VA2063-5JP32-0AF0 is a SENTRON molded case circuit breaker rated for 63 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed up to that ceiling, which simplifies panel thermal budgeting. The interrupting capacity hits 187 kA at 240 V and 121 kA at 415 V, so it handles high-fault utility feeds without cascading upstream. The ETU550 electronic release gives adjustable long-time (tr 0.5–25 s) and short-time delay (tsd up to 0.5 s), letting you coordinate selectively with downstream breakers. Front protection is IP40, meaning tools and fingers stay out, but it is not sealed against washdown — install in a clean, dry enclosure.

Mounting and integration

The 3VA2063-5JP32-0AF0 measures 105 mm wide, 181 mm tall, and 86 mm deep — a standard three-pole MCCB footprint for DIN-rail or panel-mount installation. The 86 mm depth fits typical distribution board gutters; verify gland-plate clearance if back-panel wiring is tight. The ETU550 release is field-adjustable via the front dials, so no software tool is needed for coordination setup.

Frequently asked questions

Where can I buy 3VA2063-5JP32-0AF0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is published here.

What is the interrupting capacity of 3VA2063-5JP32-0AF0 at 415 V?

121 kA at 415 V, which covers most industrial secondary-side fault levels without needing a current-limiting upstream device.

Does 3VA2063-5JP32-0AF0 require derating at high ambient temperatures?

No — the 63 A rating holds from 40 °C up to 70 °C, so no thermal derating is needed within that range.

MPN