The built-in undervoltage release (UVR) and the auxiliary contact pack — two auxiliary switches plus a trip alarm switch — mean this breaker can talk to a PLC or safety relay and drop out on a voltage-loss condition. Communication function is onboard, so you can integrate it into a higher-level monitoring scheme without an add-on module. Ground-fault detection uses summation current formation on the L-conductor, which catches leakage without a separate core-balance CT.

Siemens 3VA2063-5JQ32-0BH0 SENTRON MCCB, 63 A, 187 kA
Siemens SENTRON 3VA2063-5JQ32-0BH0, 3-pole molded case circuit breaker, 63 A rated continuous current, 187 kA breaking capacity at 240 V, ETU560 electronic trip unit, undervoltage release, communication capable.
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Product version | Line protection |
| Basic switch (supplied) ref. | 3VA2063-5JQ32-0AA0 |
| Integrated auxiliary / alarm switch ref. | 3VA9988-0AB12 |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Current at 40 °C | 63 A |
| Current at 45 °C | 63 A |
| Current at 50 °C | 63 A |
| Current at 55 °C | 60.6375 A |
| Current at 60 °C | 58.275 A |
| Current at 65 °C | 55.9125 A |
| Current at 70 °C | 53.55 A |
| Switching capacity class | M |
| Breaking capacity at 240 V | 187 kA |
| Breaking capacity at 415 V | 121 kA |
| Breaking capacity at 440 V | 121 kA |
| Breaking capacity at 500 V | 79 kA |
| Breaking capacity at 690 V | 3.4 kA |
| Power loss, max. | 7.9 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | ETU560 |
| Parameter | Value |
|---|---|
| Main circuit connection type | Lug terminal |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | Yes |
| Voltage trigger | No |
| Trip indicator | Yes |
| Communication function | Yes |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 3 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Height | 181 mm |
| Width | 105 mm |
| Depth | 86 mm |
Product details
Frequently asked questions
What is the breaking capacity of 3VA2063-5JQ32-0BH0 at 415 V?
The breaking capacity is 121 kA at 415 V, which covers most industrial distribution applications at that voltage level.
Does this MCCB include an undervoltage release?
Yes, it includes an undervoltage release (UVR) as part of the auxiliary release design, allowing automatic trip on voltage loss.
Where can I buy 3VA2063-5JQ32-0BH0 and how is it quoted?
This part is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, not a stock promise.