Breaking capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V — the 415 V figure is the one that governs most European industrial panels, and it gives real headroom above typical fault levels. Four poles, rated insulation voltage 800 V, and a maximum power loss of 5.4 W.
The 4-pole footprint matches the common 3-phase-plus-neutral distribution layout in switchboards and motor control centers.