Specifications

3VA2063-5KP32-0CL0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA2063-5KP32-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB22
3VA2063-5KP32-0CL0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.6375 A
Current at 60 °C58.275 A
Current at 65 °C55.9125 A
Current at 70 °C53.55 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V79 kA
Breaking capacity at 690 V3.4 kA
Power loss, max.7.9 W
3VA2063-5KP32-0CL0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
3VA2063-5KP32-0CL0 — Construction & Connection
ParameterValue
Main circuit connection typeLug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2063-5KP32-0CL0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts4
3VA2063-5KP32-0CL0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2063-5KP32-0CL0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm

Product details

Line protection MCCB with ETU850 — 63 A, 3-pole

It carries an ETU850 electronic trip unit with communication and measurement functions — meaning it can report current draw and trip events back to a controller, not just interrupt fault current silently. Interrupting capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 3.4 kA at 690 V. Thermal derating is minimal up to 50 °C (full 63 A), then drops to 60.6 A at 55 °C, 58.3 A at 60 °C, 55.9 A at 65 °C, and 53.6 A at 70 °C.

Auxiliary releases and switch complement

That gives four signal paths for the PLC: breaker open/closed, trip event, and a separate electrical alarm.

Mechanical endurance is rated at 20,000 operations — typical for a 63 A MCCB frame used in distribution rather than frequent motor switching. For higher-cycle applications (conveyor start/stop), consider a contactor downstream.

Dimensions are 181 mm height, 105 mm width, 86 mm depth.

Frequently asked questions

How do I get current pricing and availability for 3VA2063-5KP32-0CL0?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels — no automated price or stock count is published here.

What is the interrupting capacity of this MCCB at different voltages?

187 kA at 240 V, 121 kA at 415 V and 440 V, 79 kA at 500 V, and 3.4 kA at 690 V. The 187 kA rating at 240 V is the highest — suitable for high-fault locations like transformer secondaries.

What auxiliary contacts does this breaker include?

It ships with 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ type), plus an integrated undervoltage release. The basic switch supplied is 3VA2063-5KP32-0AA0.

What are the mounting dimensions of 3VA2063-5KP32-0CL0?

Height 181 mm, width 105 mm, depth 86 mm. The 105 mm width fits a standard 3-pole MCCB footprint on DIN rail or bolted mounting.