Siemens 3VA2063-5KP32-0HA0 SENTRON MCCB, 63A, 187kA at 240V

MPN3VA2063-5KP32-0HA0

Siemens SENTRON 3VA2063-5KP32-0HA0, molded case circuit breaker, 3-pole, 63 A rated continuous current, 187 kA interrupting capacity at 240 V AC, line protection design with shunt trip release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2063-5KP32-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA20635KP320AA0

Ratings

3VA2063-5KP32-0HA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.5.4 W

Protection & Trip Unit

3VA2063-5KP32-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU850
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA2063-5KP32-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2063-5KP32-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA2063-5KP32-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2063-5KP32-0HA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

The 3VA2063-5KP32-0HA0: This 3-pole unit carries a shunt trip release (STL) for remote tripping and a communication function for integration into a monitored distribution scheme, but no undervoltage release and no ground-fault monitoring — if your spec calls for undervoltage protection or GFCI, you need a different variant in the 3VA2 family.

Dimensions are 105 mm wide by 181 mm tall by 86 mm deep — the 105 mm width is a standard 3-pole MCCB footprint for Siemens SENTRON, so it drops into existing 3VA2 panel cutouts without re-drilling the gland plate. Rated insulation voltage is 800 V, with a maximum power loss of 5.4 W, so thermal management inside the enclosure is minimal.

Frequently asked questions

What is the interrupting capacity of 3VA2063-5KP32-0HA0 at 240 V?

187 kA at 240 V AC, which drops to 121 kA at 415 V and 75.6 kA at 500 V — the 690 V rating is only 3 kA, so this breaker is not suited for high-voltage distribution.

Will 3VA2063-5KP32-0HA0 drop into a panel specified around 5SQ2370-2YA05 without rewiring?

The 105 mm width and standard SENTRON mounting footprint mean it fits the same panel cutout as most 3-pole MCCBs in this class, but the 5SQ2370-2YA05 is a different manufacturer's product — verify terminal spacing and lug type against your existing bus bars before ordering; no direct drop-in guarantee exists between brands.

Where can I buy 3VA2063-5KP32-0HA0?

Sourced and quoted to order against an RFQ through independent distribution — availability and current pricing are confirmed at quote time.

MPN