Skip to main content
Siemens 3VA2063-6HN32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2063-6HN32-0AH0 SENTRON MCCB, 63 A, 242 kA at 240

MPN3VA2063-6HN32-0AH0

Siemens SENTRON 3VA2063-6HN32-0AH0, molded case circuit breaker, 3-pole, 63 A, ETU350 electronic trip unit, 242 kA at 240 V, IP40 front, current production.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA2063-6HN32-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA20636HN320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA2063-6HN32-0AH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3 kA
Power loss, max.5.4 W

Protection & Trip Unit

3VA2063-6HN32-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
Overcurrent protection functionLSI
Ground-fault monitoringWithout

Construction & Connection

3VA2063-6HN32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA2063-6HN32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA2063-6HN32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA2063-6HN32-0AH0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

63 A continuous, flat across the thermal range

The Siemens 3VA2063-6HN32-0AH0 is a SENTRON molded case circuit breaker rated for 63 A continuous current from 40 °C all the way up to 70 °C — no derating curve to chase in a warm panel. Breaking capacity hits 242 kA at 240 V, 187 kA at 415 V and 440 V, then 121 kA at 500 V, dropping to 3 kA at 690 V. That's a high-interrupting rating for a 63 A frame; it clears severe fault currents without cascading upstream breakers in most distribution designs. The ETU350 electronic trip unit gives you adjustable long-time, short-time, instantaneous, and ground-fault protection curves — field-configurable via the front dials. No undervoltage release, no communication module, no voltage trigger on this variant; it's a straight line-protection breaker with 2 auxiliary switches plus a trip alarm switch (HQ type) for status feedback to a PLC or annunciator.

Panel fit and environmental limits

Three-pole, 105 mm wide, 181 mm tall, 86 mm deep — mounts into a standard SENTRON distribution board or standalone enclosure. IP40 on the front means it's protected against tools and wires >1 mm, but not against water ingress; keep it inside a cabinet or switchgear assembly. Operating range from -25 °C to 70 °C, storage from -40 °C to 80 °C. Maximum power loss is 5.4 W — negligible for thermal budgeting in a multi-breaker panel.

Frequently asked questions

What is the breaking capacity of this MCCB at 240 V?

242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3 kA at 690 V.

Where can I buy 3VA2063-6HN32-0AH0?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What trip unit does this breaker use?

ETU350 electronic trip unit with adjustable long-time, short-time, instantaneous, and ground-fault protection curves.

Does the 3VA2063-6HN32-0AH0 include auxiliary contacts?

Yes, it comes with 2 auxiliary switches plus 1 trip alarm switch (HQ type).

MPN
3VA2063-6HN32-0AH0